41
MITSUBISHI ELECTRIC
/ P SERIES R32
SIZE
MODEL
DIAMETER
EXTERNAL PIPING
REFRIGERANT CHARGE
ELECTRICAL DATA
Liquid mm
(inches)
Gas mm
(inches)
Max
Height
Max
Lenght*
Max
Pipe Bends
Precharge
Kg*
Precharge
lenght
mt.
Additional
charge
g/mt
tonCO
2
eq
precharge*
tonCO
2
eq
max charge*
Operating
current
max
Breaker
71
SUZ-SM
9,52 (3/8")
15,88 (5/8")
30
30
10
1,45
7
40
0,98
1,60
1
25 A
100
PUZ-SM
9,52 (3/8")
15,88 (5/8")
30
30
15
3,10
30
2,09
2,09
1 / 3
32 A / 16 A
125
9,52 (3/8")
15,88 (5/8")
30
40
15
3,60
2,43
3,51
1 / 3
32 A / 16 A
140
9,52 (3/8")
15,88 (5/8")
30
40
15
3,60
2,43
3,51
1 / 3
40 A / 16 A
SUZ-SM / PUZ-SM
S/P SERIES - OUTDOOR UNIT -
Smart
L
N
230V
Breaker
S1
S2
S3
S1
S2
S3
SUZ / PUZ-SM
Indoor unit
L2
L1
L3
N
380V
Breaker
Three-phase connection
Exemple of total additional charge calculation
Formula
∆W(g) = [Lenght of pipes (m) -
Precharge lenght (m)] x additional charge (g/m)
Example
Outdoor unit
= PUZ-SM125VA
Total pipes lenght
(inlet piping only) = 35 m
Lenght with additional charge
(as tab) = 30 m
Additional charge = 40 g/m
Calculation: ∆W(g) = [35 - 30] x 20 = 100 g
MIN AREA according to standard CEI EN 60335-2-40 ED6 R32 - HUMAN COMFORT
UNIT
Max charge (kg)
Min Area (m²)
INDOOR
OUTDOOR
WALL MOUNTED
71
2,37
5,31
100
3,10
9,09
125
4,00
15,13
140
4,00
15,13
CEILING - DUCTED
71
2,37
3,56
100
3,10
6,08
125
4,00
10,13
140
4,00
10,13
Содержание M-SERIES
Страница 1: ...Practical installation guide DX ...
Страница 2: ......
Страница 3: ......
Страница 5: ...3 ...
Страница 37: ...35 ...
Страница 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Страница 49: ...47 ...
Страница 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Страница 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Страница 76: ...74 Ventilation ...
Страница 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Страница 111: ...109 ...
Страница 118: ......
Страница 119: ......