background image

2

Specifications are subject to change without notice.  

                                                                              © 2019 Mitsubishi Electric US, Inc.

Contents

1. Control box component identification

2. Operating sequence

LAHK-1 Control Box Component Identification

Operating Sequence

Outdoor Unit in Cooling Mode

The LAHK-1 low ambient hood is designed to reduce 

the airflow through the outdoor units as the ambient 

temperature drops. This maintains the head pressure

at a level that will allow the system to perform at 100% 

capacity down to -10

o

F outdoor temperature.

A thermistor mounted on the side of the unit senses 

the outdoor temperature. As the outdoor temperature 

drops, the resistance of the thermistor increases. The

thermistor is connected to the specially designed circuit 

board and the resistance value from the thermistor is 

converted to a DC voltage output within the circuit 

board. This DC voltage output drives the damper 

actuator to a predetermined position based on the 

outdoor temperature.

The inverter driven fan motor will adjust the discharge 

pressure based on system capacity demand. The 

motor will speed up and force more air through the 

damper if there is a higher system capacity demand, or 

slow down if system capacity demand decreases.

Outdoor Unit in Heating Mode

Heating mode requires the damper be in the fully open 

position to allow full airflow and maximum heating 

capacity.

Heating mode automatically deactivates the kit through 

an interlock relay. The coil for this relay is tied into the 

reversing valve connection on the outdoor unit. When 

the unit switches to heating mode, the reversing valve 

is energized. This in-turn energizes the interlock relay. 

When the relay is energized, the normally closed 

contact opens. By opening this contact, the power to 

the transformer and control board is interrupted, this 

allows the damper to spring to the full open position.

Outdoor Unit in Defrost Mode

If the outdoor unit will be running in heating mode, a 

defrost period is inevitable. During defrost the low 

ambient controls see this as the unit operating in

cooling mode. If the outdoor temperature is below 50 F, 

the damper will close to a position equal to that 

required during the cooling cycle. Once the unit comes 

back out of defrost and into heating mode, the damper 

will again spring wide open for full airflow.

Operation Test

Outdoor unit must be in cooling mode

December 2013

© 2013 Mitsubishi Electric US, Inc.

2

Outdoor unit in cooling mode

The LAHN-1/LAHN-3 low ambient hood is designed to reduce the 

airflow through the outdoor units as the ambient temperature drops. 

This maintains the head pressure at a level that will allow the system 

to perform at full capacity down to -10°F outdoor temperature.

A  thermistor  mounted  on  the  side  of  the  unit  senses  the  outdoor 

temperature.  As  the  outdoor  temperature  drops,  the  resistance  of 

the thermistor increases. The thermistor is connected to the specially 

designed circuit board and the resistance value from the thermistor 

is converted to a DC voltage output within the circuit board. This DC 

voltage output drives the damper actuator to a predetermined position 

based on the outdoor temperature.

The inverter driven fan motor will adjust the discharge pressure based 

on system capacity demand. The motor will speed up and force more 

air through the damper if there is a higher system capacity demand, 

or slow down if system capacity demand decreases.

Outdoor unit in heating mode

Heating  mode  requires  the  damper  be  in  the  fully  open  position  to 

allow full airflow and maximum heating capacity.

Heating mode automatically deactivates the kit through an interlock 

relay. The coil for this relay is tied into the reversing valve connection 

on  the  outdoor  unit.  When  the  unit  switches  to  heating  mode,  the 

reversing valve is energized. This in turn energizes the interlock relay. 

When the relay is energized, the normally closed contact opens. By 

opening this contact, the power to the transformer and control board is 

interrupted, this allows the damper to spring to the full open position.

Outdoor unit in defrost mode

If the outdoor unit will be running in heating mode, a defrost period 

is inevitable. During defrost the low ambient controls see this as the 

unit operating in cooling mode. If the outdoor temperature is below 

40°F, the damper will close to a position equal to that required during 

the cooling cycle. Once the unit comes back out of defrost and into 

heating mode, the damper will again spring wide open for full airflow.

Operation test

Outdoor unit must be in cooling mode.

All hoods and damper controls are tested at the factory before shipping. 

To perform an operational test once the installation is complete, follow 

the steps below. Please refer to the chart and table below for detailed 

control logic.

Operation testing when the outdoor ambient is ABOVE 40°F

1.  Turn on power to the outdoor unit.

1. Control box component identification .....................................

2

2. Operating sequence ...............................................................

2

3. Damper blade adjustment ......................................................

5

4. Damper actuator manual override  .........................................

8

5. Parts list ..................................................................................

9

6. Wiring diagram .....................................................................10

Содержание LAHN-1

Страница 1: ...I ELECTRIC US INC CITY MULTI PUHY P T Y S NU A BS PUHY EP T Y S NU A BS and PUHY HP T Y S NU A Series Outdoor Units for use with 2019 TECHNICAL SERVICE MANUAL Model LAHN 1 LAHN 3 Low Ambient Hood 4000292 2015 TECHNICAL SERVICE MANUAL Model LAHK 1 Low Ambient Hood 4000292 ...

Страница 2: ...HN 1 LAHN 3 low ambient hood is designed to reduce the airflow through the outdoor units as the ambient temperature drops This maintains the head pressure at a level that will allow the system to perform at full capacity down to 10 F outdoor temperature A thermistor mounted on the side of the unit senses the outdoor temperature As the outdoor temperature drops the resistance of the thermistor incr...

Страница 3: ... take 10 20 seconds for the internal thermistor temperature to drop The damper will start to move toward the closed position after the thermistor drops below 50 F 5 Once the thermistor warms above 50 F it will move back to the full open position indicating the low ambient kit is working as designed eration testing when the outdoor ambient is LOW 50 F 1 Turn on power to the outdoor unit 2 Make sure...

Страница 4: ... switches to heating mode the coil of the relay is energized opening this contact This in turn de energizes the transformer disconnecting power to the low ambient kit control circuitry This allows the damper to spring return to the full open position during heating mode To check make sure the contact is closed when the outdoor unit is in cooling mode coil de energized and the contact is open when ...

Страница 5: ...on 4 Set the damper to approx open Use the damper crank handle as spacer 5 Re tighten U bolts on damper shaft 6 Release the motor by slightly cranking with the handle Check the operation manually 7 The goal is to have opening on the damper assembly in the 85 degree position 100 The damper should never be 100 closed during operation When working properly the damper will be approximately 95 closed a...

Страница 6: ...egree position 5 Close the blades by hand and insert Crank handle under damper blade near the screws as shown to ensure it is open approximately inch at 85 degrees 6 4 Using the crank handle turn the motor counterclockwise until the indicator snugs against the stop at 85 degrees Loosen the Philips head screw for the mechanical stop Slide the mechanical stop to 85 halfway between 8 and 9 and tighte...

Страница 7: ... Ensure end of shaft is flush to edge of clamp black surface as shown 8 Slightly crank the handle to release the motor The damper will return to the open position 7 Slightly crank the handle to release the motor The damper will return to the open position 8 Review and Manual Test To ensure the LAHK unit is functioning as designed Crank the Belimo motor back to the 85 degree position and visually c...

Страница 8: ...04 60 o 30 34 562 7 90 70 o 25 39 917 8 75 80o 20 46 220 9 16 85 o Below 20 o F N A 9 16 85 o Follow the instructions below for manually positioning and locking the damper in place IMPORTANT Disconnect power to the damper motor before locking in place The damper actuator comes with a crank handle attached to manually move the damper position The crank handle is removable and if it s missing a 3 16...

Страница 9: ...ss assy TH LAHK 1 A CN505 Connector HC LAHK 1 1A CNAC2 Connector HC LAHK 1 2A Wire Harness Components CN505 Connector Part Number HC LAHK 1 1A Includes everything shown White CNAC2 Connector Part Number HC LAHK 1 2A Includes everything shown Black Note Damper linkage parts can be purchased locally If damper blades or complete assembly needs replacing order new LAHN 2 LAHN 4 hood and damper assembl...

Страница 10: ... wire that corresponds to the outdoor unit supply voltage as shown below CN505 Connection CNAC2 1 amp on the board Connect the white wire male For Use with Modular N Generation Y Series Outdoor Units Only plug with four wires onto the spare connection 208 volt orange wire female connector move and secure cap to unused wire the CN505 connection Connect the white the CN505 connection Plug the white ...

Страница 11: ...11 2019 Mitsubishi Electric US Inc Specifications are subject to change without notice ...

Страница 12: ...e to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the commercial environment Manufactured for MITSUBISHI ELECTRIC US INC www mylinkdrive com Toll Free 800 433 4822 MEUS DOC MD 1922 K002 Ver 2 November 2019 ...

Отзывы: