3. Damper blade adjustment

IMPORTANT! 

It’s possible that during shipping, the damper shaft may have 

moved in the actuator shaft clamp assembly.

In  some  cases  due  to  manufacturing  tolerances  the  LAHN  blades 

could  close  100%. 

The damper should never be 100% closed 

during operation. 

  When  working  properly  the  damper  will  be 

approximately 95% closed at -5°F and below. The following procedure 

will allow proper adjustment.

The Belimo damper motor within the LAHN control box has a built in 

mechanical stop to adjust the maximum angle of rotation. This must 

be adjusted to 85 degrees and the damper blade position verified or 

re-set to the proper position (1/4” open) to ensure the unit functions 

properly.

Belimo motor angle indicating 

 

scale shown below.

The factory setting for the mechanical stop 

 

is shown below at 85 degree hood angle.

IMPORTANT! ENSURE POWER IS OFF BEFORE STARTING!! 

Basic service overview

1.  Set the damper motor stop to 85 degrees.

2.  Loosen “U” bolts on damper shaft.

3.  Crank the motor against the 85-degree stop then lock into 

position.

4.  Set the damper to approx. ¼” open. 

 

(Use the damper crank handle as spacer.)

5.  Re-tighten “U” bolts on damper shaft.

6.  Release the motor by slightly cranking with the handle. 

 

Check the operation manually.

7.  The goal is to have ¼” opening on the damper assembly 

 

in the 85 degree position.

LOW AMBIENT HOOD – LAHK-1   DAMPER BLADE ADJUSTMENT

 

IMPORTANT!

 

It’s possible that during shipping, the damper shaft may have moved in the actuator shaft 

clamp assembly.

 In some cases due to manufacturing tolerances the LAHK blades could close 

100%. 

The damper should never be 100% closed during operation.  

When working properly 

the damper will be approximately 95% closed at 20 degrees and below. The following 

procedure will allow proper adjustment. 
The Belimo damper motor within the LAHK control box has a built in mechanical stop to 
adjust the maximum angle of rotation. This must be adjusted to 85 degrees and the damper 
blade position verified or re-set to the proper position 

(1/4” open) 

to ensure the unit 

functions properly. 

The factory setting for the mechanical 

stop is shown below at 95. 

Belimo motor angle indicating 

scale shown below.

 

IMPORTANT!   ENSURE POWER IS OFF BEFORE STARTING!!

 

Basic Service Overview 

1.) Set damper motor stop to 85 degrees. 

2.) Loosen “U” bolts on damper shaft 

3.) Crank motor against 85 degree stop then lock into position 

4.) Set damper to approx. ¼” open. (Use damper crank handle as spacer.) 

5.) Re-Tighten “U” bolts on damper shaft 

6.) Release motor by slightly cranking with handle. Check operation manually 

7.) The goal is to have ¼” opening on damper assembly in the 85 degree position. 

Содержание LAHN-1

Страница 1: ...I ELECTRIC US INC CITY MULTI PUHY P T Y S NU A BS PUHY EP T Y S NU A BS and PUHY HP T Y S NU A Series Outdoor Units for use with 2019 TECHNICAL SERVICE MANUAL Model LAHN 1 LAHN 3 Low Ambient Hood 4000292 2015 TECHNICAL SERVICE MANUAL Model LAHK 1 Low Ambient Hood 4000292 ...

Страница 2: ...HN 1 LAHN 3 low ambient hood is designed to reduce the airflow through the outdoor units as the ambient temperature drops This maintains the head pressure at a level that will allow the system to perform at full capacity down to 10 F outdoor temperature A thermistor mounted on the side of the unit senses the outdoor temperature As the outdoor temperature drops the resistance of the thermistor incr...

Страница 3: ... take 10 20 seconds for the internal thermistor temperature to drop The damper will start to move toward the closed position after the thermistor drops below 50 F 5 Once the thermistor warms above 50 F it will move back to the full open position indicating the low ambient kit is working as designed eration testing when the outdoor ambient is LOW 50 F 1 Turn on power to the outdoor unit 2 Make sure...

Страница 4: ... switches to heating mode the coil of the relay is energized opening this contact This in turn de energizes the transformer disconnecting power to the low ambient kit control circuitry This allows the damper to spring return to the full open position during heating mode To check make sure the contact is closed when the outdoor unit is in cooling mode coil de energized and the contact is open when ...

Страница 5: ...on 4 Set the damper to approx open Use the damper crank handle as spacer 5 Re tighten U bolts on damper shaft 6 Release the motor by slightly cranking with the handle Check the operation manually 7 The goal is to have opening on the damper assembly in the 85 degree position 100 The damper should never be 100 closed during operation When working properly the damper will be approximately 95 closed a...

Страница 6: ...egree position 5 Close the blades by hand and insert Crank handle under damper blade near the screws as shown to ensure it is open approximately inch at 85 degrees 6 4 Using the crank handle turn the motor counterclockwise until the indicator snugs against the stop at 85 degrees Loosen the Philips head screw for the mechanical stop Slide the mechanical stop to 85 halfway between 8 and 9 and tighte...

Страница 7: ... Ensure end of shaft is flush to edge of clamp black surface as shown 8 Slightly crank the handle to release the motor The damper will return to the open position 7 Slightly crank the handle to release the motor The damper will return to the open position 8 Review and Manual Test To ensure the LAHK unit is functioning as designed Crank the Belimo motor back to the 85 degree position and visually c...

Страница 8: ...04 60 o 30 34 562 7 90 70 o 25 39 917 8 75 80o 20 46 220 9 16 85 o Below 20 o F N A 9 16 85 o Follow the instructions below for manually positioning and locking the damper in place IMPORTANT Disconnect power to the damper motor before locking in place The damper actuator comes with a crank handle attached to manually move the damper position The crank handle is removable and if it s missing a 3 16...

Страница 9: ...ss assy TH LAHK 1 A CN505 Connector HC LAHK 1 1A CNAC2 Connector HC LAHK 1 2A Wire Harness Components CN505 Connector Part Number HC LAHK 1 1A Includes everything shown White CNAC2 Connector Part Number HC LAHK 1 2A Includes everything shown Black Note Damper linkage parts can be purchased locally If damper blades or complete assembly needs replacing order new LAHN 2 LAHN 4 hood and damper assembl...

Страница 10: ... wire that corresponds to the outdoor unit supply voltage as shown below CN505 Connection CNAC2 1 amp on the board Connect the white wire male For Use with Modular N Generation Y Series Outdoor Units Only plug with four wires onto the spare connection 208 volt orange wire female connector move and secure cap to unused wire the CN505 connection Connect the white the CN505 connection Plug the white ...

Страница 11: ...11 2019 Mitsubishi Electric US Inc Specifications are subject to change without notice ...

Страница 12: ...e to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the commercial environment Manufactured for MITSUBISHI ELECTRIC US INC www mylinkdrive com Toll Free 800 433 4822 MEUS DOC MD 1922 K002 Ver 2 November 2019 ...

Отзывы: