![Mitsubishi Electric GX Configurator-SC Скачать руководство пользователя страница 310](http://html.mh-extra.com/html/mitsubishi-electric/gx-configurator-sc/gx-configurator-sc_user-manual_239043310.webp)
10 - 28 10 - 28
MELSEC-Q
10 DEDICATED INSTRUCTIONS
10.7.1 Functional protocol
The following functions are available by executing functional protocols with the
CPRTCL instruction.
Receive data clear
Send/receive data monitoring start/stop
RS/DTR signal condition designation
(1) Setting
Specify the functional protocol number of the function to be executed in the
control data ((S)+2 to (S)+9) of the CPRTCL instruction.
For details of the CPRTCL instruction, refer to Section 10.7.
(2) List of functional protocols
The following table lists the functional protocols described in this section.
Protocol
number
Protocol type
Keyword
1
Reference
201
Receive data clear
Receive Data
Clear
(a) in this section
202
Send/Receive data monitoring start
Send/Recv
Monitor Start
(b) in this section
203
Send/Receive data monitoring stop
Send/Recv
Monitor Stop
204
Turns ER(DTR) signal ON
DTR ON
(c) in this section
205
Turns ER(DTR) signal OFF
DTR OFF
206
Turns RS(RTS) signal ON
RS ON
207
Turns RS(RTS) signal OFF
RS OFF
1: Character strings that are stored to the protocol name of the protocol
execution log when functional protocols are executed.
(a) Receive data clear
Receive data in the OS area are cleared.
(b) Send/Receive data monitoring start/stop
Start or stop of send/receive data monitoring is specified.
When the functional protocol (202, 203) is executed, a monitoring start
command (0001
H
) or monitoring stop command (0000
H
) is set for
send/receive data monitoring designation (address: 2018
H
/2118
H
) in the
QJ71C24N(-R2/R4).
For details of send/receive monitoring, refer to the User's Manual
(Application).
(c) RS/DTR signal status specification
ON/OFF status of the RS(RTS)/ER(DTR) signal is specified.
When the functional protocol (204 to 207) is executed, corresponding bits of
the RS/DTR signal status designation (address: 92
H
/132
H
) are turned
ON/OFF in the QJ71C24N(-R2/R4).
For details of RS/DTR signal status designation, refer to Section 3.2.1.
Содержание GX Configurator-SC
Страница 2: ......
Страница 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 138: ...4 35 4 35 MELSEC Q 4 SETTINGS AND PROCEDURES PRIOR TO OPERATION MEMO ...
Страница 397: ...App 24 App 24 MELSEC Q APPENDICES Connection example 3 Connection example 4 ...
Страница 439: ...WARRANTY ...
Страница 441: ......