3-3. Supplying power to the M-NET transmission lines
GB-50ADA has a built-in function to supply power to the M-NET transmission line. (power supply coefficient: 6)
The total power consumption coefficient of the system controller and M-NET remote controller to which GB-50ADA supplies
power (See table 1) should not exceed the power supply coefficient of GB-50ADA, which is six.
Table 1
Power consumption coefficient of the controller
Table 2
No. of connectable units
Table 3
No. of connectable units in systems with various combinations of remote controllers
V: connectable
System controller
M-NET remote controller
ON/OFF remote controller
System remote controller
Schedule timer
Group remote controller
ME remote controller
LOSSNAY remote controller
1
0.5
0.25
System controller
M-NET remote controller
ON/OFF remote controller
System remote controller
Schedule timer
Group remote controller
ME remote controller
LOSSNAY remote controller
6 units
12 units
24 units
Total number of ON/OFF remote controllers
0
1
2
3
4
5
6
Total number of system remote controllers,
schedule timers, and group remote
controllers combined.
0
V
V
V
V
V
V
V
1
V
V
V
V
V
V
2
V
V
V
V
V
V
3
V
V
V
V
V
4
V
V
V
V
V
5
V
V
V
V
6
V
V
V
V
7
V
V
V
8
V
V
V
9
V
V
10
V
V
11
V
12
V
Note
When connecting both GB-50ADA and BAC-HD150 (BM ADAPTER) to the same M-NET system, certain
restrictions apply.
Consult your dealer for details.