- 26 -
To copy the data to USB memory and to read the dada from USB memory, refer to the table below and section 11-1 “switch setting”.
11 Copy to USB memory and read from USB memory
Item
No.
SW601
[0: OFF, 1: ON]
Setting items
Explanation
Notes
1
2
3
4
5
6
7
8
250
1
1
1
1
1
0
1
0
Copy to USB
memory
(0) Initial setting
data and User
info data
Set to SW606: “0”; SW607: “0”
Copy the Initial setting data and the User info
data to the \[“GB_” + Serial Number] folder in the
root folder of the USB memory.
Initial setting data
and User info data
(1) Initial setting
data
Set to SW606: “0”; SW607: “1”
Copy the Initial setting data to the \[“GB_” +
Serial Number] folder in the root folder of the
USB memory.
(8) User info
data
Set to SW606: “0”; SW607: “8”
Copy the user info data to the \[“GB_” + Serial
Number] folder in the root folder of the USB
memory.
(9) Charge
parameter
data
Set to SW606: “0”; SW607: “9”
Copy the Charge parameter data to the \[“GB_” +
Serial Number]\ChargeParameters\[Date] folder in
the root folder of the USB memory in the CSV
format.
Refer to section 11-2-1 ”Charge parameter data”.
Saving the Charge
parameter data and
Power consumption
data may take
several dozens of
minutes.
(10) Power
consumption
data
Set to SW606: “0”; SW607: “A”
Copy the Power consumption data to the \[“GB_” +
Serial Number]\ChargeParameters\[Date] folder in
the root folder of the USB memory in the CSV
format.
Refer to section 11-2-2 ”Power consumption data”
251
1
1
1
1
1
0
1
1
Read from
USB memory
Initial setting
data and User
info data
Set to SW606: “0”; SW607: “0”
Read the data from USB memory.
Create [“SetupData_” + IP address]
*1
or
[“SetupData”] folder in the root folder of the USB
memory using PC.
*2
Save the setting data
*3
in the folder.
*1: When the IP address of GB-50ADA is
“192.168.1.1”, the folder name will be
[SetupData_192_168_1_1].
*2: If both [“SetupData_” + IP address] folder and
[“SetupData” ] folder exist, the data from
[“SetupData_” + IP address] folder will be read.
*3: “(0) Initial setting data and User info data” or
“(1) Initial setting data” or “(8) User info data”
Reset the power
after all settings
have been made.
Note
Use a USB memory that supports USB 1.1 standards.
Some security-enhanced USB memories cannot be used.
The following USB memories are checked for proper operation. (As of Oct. 2009)
a: Manufacturer: Sandisk
Model: SDCZ6-2048-J65RB
Capacity: 2G
b: Manufacturer: Kingston
Model: DT400/2GBFE
Capacity: 2G
c : Manufacturer: I-O DATA
Model: TB-BH2/2G/*
Capacity: 2G
d: Manufacturer: I-O DATA
Model: TB-BH2/4G/*
Capacity: 4G
e: Manufacturer: BUFFALO
Model: RUF-C2GS-**/U2
Capacity: 2G
f : Manufacturer: BUFFALO
Model: RUF2-C2GS-**/M
Capacity: 2G
g: Manufacturer: BUFFALO
Model: RUF-C4GS-**/U2
Capacity: 4G
h: Manufacturer: BUFFALO
Model: RUF-C8GS-**/U2
Capacity: 8G
i : Manufacturer: adata
Model: C702
Capacity: 2G
(* or ** in the models of c through h indicates color. )
* Use FAT32 or FAT16
to format a USB