Sequence control example with self-holding function and PLF
When executing a control target in sequence control, create "Operation memory 1" and create an actual
control program with the condition of "Operation memory 1".
"Operation memory 1"of the actual control program is reset with "Completed PLS 1".
To proceed to the next process, create "Next process PLF", which is a falling signal, to turn off
"Operation memory 1" and start "Operation memory 2".
Operation memory 1
Next process PLF
Proceed to the next process
****Process JOB 1 program****
M101
Sequence
memory
M102
Start PLS
M111
Completed
PLS 1
M110
Operation
memory 1
M110
Operation
memory 1
M110
Operation
memory 1
X1
Completion
condition 1
PLS
M111
Completed
PLS 1
M110
Operation
memory 1
PLF
M112
Next process
PLF 1
****Process JOB 2 program****
M101
Sequence
memory
M112
Next process
PLF 1
M121
C ompleted
PLS 2
M120
Operation
memory 2
M120
Operation
memory 2
M120
Operation
memory 2
X2
Completion
condition 2
PLS
M121
Completed
PLS 2
M120
Operation
memory 2
PLF
M122
Next process
PLF 2