9 Command Interface
9.1 [BFM #1000 to #1066] Command Interface (CIF)
72
FX
3U
-J1939 User's Manual
9. Command Interface
This chapter describes the Command Interface supported by FX
3U
-J1939.
A function overview of the Command Interface is shown in the following table.
*1.
FX
3U
-J1939 firmware Ver. 1.10 or later is applicable.
9.1
[BFM #1000 to #1066] Command Interface (CIF)
The CIF can be used for asynchronous services, configuration and diagnosis.
For all commands, the parameter (BFM #1001 to #1066) must be set first. When the command code is written
to BFM #1000, the command is executed and BFM #1000 shows HFFFF (CIF busy). BFM #1000 to #1066
must not be changed until a positive or negative acknowledge is displayed in BFM #1000.
For details, refer to descriptions of each CIF command and the error code list of CIF.
For the error code list of CIF, refer to Section 9.8
Command
Function Mode Selection
Reference
J1939
Communication
Mode
Layer 2
Communication
(11 bit ID) Mode
Layer 2
Communication
(29 bit ID) Mode
Sending Layer 2 Message
-
Section 9.2
Sending PGN
-
-
Section 9.3
Request PGN
*1
-
-
Section 9.4
Setup PLC RUN>STOP messages
-
-
Section 9.5
Reset command interface
Section 9.6
Display current Parameter
Section 9.7
BFM No.
Description
TO (Write Access)
FROM (Read Access)
BFM #1000
Command code (trigger for command execution)
Command execution result code
BFM #1001 to #1066
Command parameter
Command parameter read back or
detailed error information