[Wiring Instructions]
WARNING
Before mounting or wiring the module, make sure to shut off all of the external power supply.
Failure to do so may cause electric shocks or damage the module.
When turning on the power and operating after mounting or wiring the module, make sure to
install the accessory terminal covers to the product.
Otherwise, it may cause electric shocks.
CAUTION
Make sure to place the communication cables and the power cables in a duct or fasten them
using a clamp.
If the cables are not placed in a duct or fastened with a clamp, their positions can be unstable,
moved and pulled inadvertently. This may damage the module and the cables, or cause the
module malfunction due to unsecured cable connections.
When disconnecting the communication cables and the power cables, do not pull the cables.
When disconnecting a cable with a connector, hold the connector to the module by hand and
pull it out to remove the cable.
When disconnecting a cable connected to a terminal block, loosen the screws on the terminal
block before removing the cable.
If a cable is pulled while being connected, it may cause the module malfunction or damage the
module and the cable.
Do not bundle the control line and the communication cables together with or lay it close to the
main circuit or power line. As a guideline, lay the control line and the communication cables at
least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
Before connecting twisted pair cables, the ground pin brush grounded via a resistor enables
discharging static electricity on the cables effectively. This can prevent the electrostatic
discharge to the product.