9 Troubleshooting
9.3 Error Code List
119
FX
3U
-ENET-ADP User's Manual
1
Introduc
tion
2
Specifi
cation
3
Sy
stem
Configurati
on
4
Ins
tal
lation
5
Wi
rin
g
6
Introduction of
Functi
on
s
7
C
omm
uni
cation
U
sing
M
C
Protocol
8
The O
perati
on
of G
X
W
ork
s2
9
Troubl
es
hooti
ng
A
Li
st of S
peci
al
Dev
ices
9.3
Error Code List
9.3.1
Error code of Ethernet communication
This section explains the error codes (abnormal codes) for errors that may occur in each processing when
communicating between the Ethernet adapter and an external device as well as those generated by
processing requests from the local station's FX series PLC.
Error Code List
Error
Code
(decimal)
Description
Corrective action
ERR.
LED
21
An error is detected in the PLC main unit.
•
When an error has occurred in the PLC,
take countermeasures in accordance with
the contents of the error.
•
Replace the PLC and/or Ethernet adapter.
On
22
101
ROM error
•
Check the connection status of connectors.
•
Check whether the Ethernet adapter is used
within the general specification range.
•
Check whether the power capacity is
sufficient.
•
Check based on the manual of the Ethernet
adapter and PLC main unit whether the
hardware is in normal status. For repair,
contact your local Mitsubishi Electric
representative.
•
If a problem cannot be solved by the above
actions, confirm the operation/
communication status when the error
occurred and the error log in the Ethernet
adapter. Contact your local Mitsubishi
Electric branch office or representative, and
report the confirmed information.
102
103
104
120
An error is detected in the PLC main unit.
•
When an error has occurred in the PLC,
take countermeasures in accordance with
the contents of the error.
•
Replace the PLC and/or Ethernet adapter.
750
Sum error has occurred in a parameter.
Set the parameter again, and start up the
system again.
751
The set value of a parameter is abnormal.
Check the version of the Ethernet adapter, PLC
main unit and MELSOFT.
752
753
The set value of the Ethernet adapter IP address is wrong.
Correct the IP address. Set the class to "A", "B"
or "C".
756
The set value of the host station port No. is outside the allowable range when
MELSOFT connection is specified. (Allowable range: 5556 only)
Correct the port No.
757
The set value of the host station port No. is outside the allowable range when
MC protocol (TCP or UDP) is specified. (Allowable range: 1025 to 5548 or
5560 to 65534)
759
The set value of the external device IP address is wrong when MC protocol
(UDP) is specified.
•
Correct the IP address. Set the class to "A",
"B" or "C".
•
Specify the default router IP address.
760
The set value of the external device port No. is outside the allowable range
when MC protocol (UDP) is specified. (Allowable range: 1025 to 5548 or
5560 to 65534)
Correct the port No.
761
The set value of the subnet mask field is outside the allowable range when
the default router IP address is specified. (Allowable range: 192.0.0.0 to
255.255.255.252)
Correct the subnet mask.
762
The set value of the subnet mask field is wrong when the default router IP
address is specified. ("1" does not continue from the first bit.)
763
The set value of the default router IP address is wrong when the default
router IP address is specified.
Correct the IP address. Set the class to "A", "B"
or "C".
Содержание FX3U-ENET-ADP
Страница 1: ...FX3U ENET ADP USER S MANUAL ...
Страница 2: ......
Страница 6: ... 4 Safety Precautions Read these precautions before use MEMO ...
Страница 160: ...154 FX3U ENET ADP User s Manual Revised History Revised History Date Revision Description 2 2012 A First Edition ...
Страница 161: ......