Additional function
2.8 Additional function
2.8.1
Remote setting function selection (Pr. 59
)
* External running frequency (other than multi-speed) or PU running frequency
Even if the operation panel is located away from the enclosure, you can use
contact signals to perform continuous variable-speed operation, without using
analog signals.
Parameter
Name
Factory
Setting
Setting
Range
Remarks
59
Remote setting
function selection
0
0, 1, 2
Setting is enabled when Pr. 30 = "1"
REMARKS
•
By merely setting this parameter, you can use the acceleration, deceleration and setting clear
functions of the motorized speed setter (FR-FK).
•
When the remote function is used, the output frequency of the inverter can be compensated
for as follows:
External operation mode
Frequency set by RH/RM operation plus external analog
frequency command
PU operation mode
Frequency set by RH/RM operation plus setting dial or PU
digital preset frequency
<Operation panel operation procedure>
* When you have set "1" in Pr. 53 "frequency setting operation selection", you need not
press the
.
Deceleration(RM)
Clear(RL)
Acceleration(RH)
Forward rotation
(STF)
Ou
tput
fr
e
q
uen
cy (H
z)
ON
ON
Power supply
ON
*
ON
ON
ON
ON
ON
When Pr. 59="2"
When Pr. 59="1"
ON
ON
ON
Monitor, frequency
setting mode
MODE
Press the to
complete setting.*
SET
Turn the setting dial
to make correction.
SET