14
6 PARAMETER
6.1 Parameter list
In the initial setting, only the simple mode parameters are displayed.
Set Pr. 160
User group read selection
as required.
Parameter
Name
Initial
Value
Setting
Range
Remarks
160
User group read selection
9999
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be
displayed.
1
Only parameters registered in the user group can be displayed.
Remarks
앫
The parameters marked
are the simple mode parameters.
앫
The parameters marked with
in the table allow its setting to be changed during operation even if "0"
(initial value) is set in Pr. 77
Parameter write selection
.
Parameter
Name
Setting Range
Initial
Value
0
Torque boost
0 to 30%
6/4/3/2/
1.5/1% *
2
1
Maximum frequency
0 to 120Hz
120/60Hz *
1
2
Minimum frequency
0 to 120Hz
0Hz
3
Base frequency
0 to 400Hz
50Hz
4
Multi-speed setting
(high speed)
0 to 400Hz
50Hz
5
Multi-speed setting
(middle speed)
0 to 400Hz
30Hz
6
Multi-speed setting
(low speed)
0 to 400Hz
10Hz
7
Acceleration time
0 to 3600/360s
5s/15s *
3
8
Deceleration time
0 to 3600/360s
10s/30s *
3
9
Electronic thermal
O/L relay
0 to 500/
0 to 3600A *
1
Rated
inverter
current
10
DC injection brake
operation frequency
0 to 120Hz,
9999
3Hz
11
DC injection brake
operation time
0 to 10s, 8888
0.5s
12
DC injection brake
operation voltage
0 to 30%
4/2/1% *
4
13
Starting frequency
0 to 60Hz
0.5Hz
14
Load pattern
selection
0, 1
1
15
Jog frequency
0 to 400Hz
5Hz
16
Jog acceleration/
deceleration time
0 to 3600/360s
0.5s
17
MRS input selection
0, 2
0
18
High speed
maximum frequency
120 to 400Hz
120/60Hz *
1
19
Base frequency
voltage
0 to 1000V,
8888, 9999
8888
20
Acceleration/
deceleration
reference frequency
1 to 400Hz
50Hz
21
Acceleration/
deceleration time
increments
0, 1
0
22
Stall prevention
operation level
0 to 120%, 9999
110%
23
Stall prevention
operation level
compensation factor
at double speed
0 to 150%, 9999
9999
24 to 27
Multi-speed setting
(4 speed to 7 speed)
0 to 400Hz,
9999
9999
28
Multi-speed input
compensation
selection
0, 1
0
29
Acceleration/
deceleration pattern
selection
0, 1, 2, 3, 6
0
30
Regenerative
function selection
0, 2, 10, 20, 100,
120/
0, 1, 2, 10, 11,
20, 21, 100, 101,
120, 121 *
1
0
31
Frequency jump 1A
0 to 400Hz,
9999
9999
32
Frequency jump 1B
0 to 400Hz,
9999
9999
33
Frequency jump 2A
0 to 400Hz,
9999
9999
34
Frequency jump 2B
0 to 400Hz,
9999
9999
35
Frequency jump 3A
0 to 400Hz,
9999
9999
Parameter
Name
Setting Range
Initial
Value
*1
The setting depends on capacities. (01160 or less/01800 or more)
*2
The setting depends on capacities. (00023/00038 to 00083/00126, 00170/00250 to 00770/00930, 01160/01800 or more)
*3
The setting depends on capacities. (00170 or less/00250 or more)
*4
The setting depends on capacities. (00170 or less/00250 to 01160/01800 or more).