16
PARAMETER
118
PU communication
speed
48, 96, 192, 384
192
119
PU communication
stop bit length.
0, 1, 10, 11
1
120
PU communication
parity check
0, 1, 2
2
121
Number of PU
communication
retries
0 to 10, 9999
1
122
PU communication
check time interval
0, 0.1 to 999.8s,
9999
9999
123
PU communication
waiting time setting
0 to 150ms,
9999
9999
124
PU communication
CR/LF presence/
absence selection
0, 1, 2
1
125
Terminal 2 frequency
setting gain
frequency
0 to 400Hz
50Hz
126
Terminal 4 frequency
setting gain
frequency
0 to 400Hz
50Hz
127
PID control
automatic
switchover
freqeuncy
0 to 400Hz,
9999
9999
128
PID action selection
10, 11, 20, 21,
40, 41, 50, 51,
60, 61, 70, 71,
80, 81, 90, 91,
100, 101, 110,
111, 120, 121,
140, 141
10
129
PID proportional
band
0.1 to 1000%,
9999
100%
130
PID integral time
0.1 to 3600s,
9999
1s
131
PID upper limit
0 to 100%,
9999
9999
132
PID lower limit
0 to 100%,
9999
9999
133
PID action set point
0 to 100%,
9999
9999
134
PID differential time
0.01 to 10.00s,
9999
9999
135
Commercial power-
supply switchover
sequence output
terminal selection
0, 1
0
136
MC switchover
interlock time
0 to 100s
1s
137
Start waiting time
0 to 100s
0.5s
138
Commercial power-
supply operation
switchover selection
at an alarm
0, 1
0
139
Automatic switcho-
ver frequency
between inverter and
commercial power-
supply operation
0 to 60Hz,
9999
9999
140
Backlash
acceleration
stopping frequency
0 to 400Hz
1Hz
141
Backlash
acceleration
stopping time
0 to 360s
0.5s
Parameter
Name
Setting Range
Initial
Value
142
Backlash
deceleration
stopping frequency
0 to 400Hz
1Hz
143
Backlash
deceleration
stopping time
0 to 360s
0.5s
144
Speed setting
switchover
0, 2, 4, 6, 8, 10,
102, 104, 106,
108, 110
4
145
PU display language
selection
0 to 7
1
147
Acceleration/
deceleration time
switching frequency
0 to 400Hz,
9999
9999
148
Stall prevention level
at 0V input
0 to 120%
110%
149
Stall prevention level
at 10V input
0 to 120%
120%
150
Output current
detection level
0 to 120%
110%
151
Output current
detection signal
delay time
0 to 10s
0s
152
Zero current
detection level
0 to 150%
5%
153
Zero current
detection time
0 to 1
0
s
0.5s
154
Voltage reduction
selection during stall
prevention operation
0, 1
1
155
RT signal function
validity condition
selection
0, 10
0
156
Stall prevention
operation selection
0 to 31, 100, 101
0
157
OL signal output
timer
0 to 25s, 9999
0s
158
AM terminal function
selection
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53,
67, 70, 86 *
1
1
159
Automatic
switchover
frequency range
from bypass to
inverter operation
0 to 10Hz, 9999
9999
160
User group read
selection
0, 1, 9999
9999
161
Frequency setting/
key lock operation
selection
0, 1, 10, 11
0
162
Automatic restart
after instantaneous
power failure
selection
0, 1, 10, 11
0
163
First cushion time for
restart
0 to 20s
0s
164
First cushion voltage
for restart
0 to 100%
0%
165
Stall prevention
operation level for
restart
0 to 120%
110%
166
Output current
detection signal
retention time
0 to 10s, 9999
0.1s
Parameter
Name
Setting Range
Initial
Value
*1
Setting of "9" can be made for the 01800 or more.