Function assignment of external terminal and control
∗1
When
Pr. 59 Remote function selection
= "1" or "2", the functions of the RL, RM and RH signals are changed as given in the table.
∗2
When
Pr. 270
Stop-on contact control selection
= "1", functions of RL and RT signals are changed as in the table.
∗3
The OH signal turns ON when the relay contact "opens".
(2) Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
3
RT
Second function selection
Pr. 44 to Pr. 51
Pr. 270
= 1
Stop-on contact selection 1
Pr. 270, Pr. 275, Pr. 276
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
7
OH
External thermal relay input
∗3
Pr. 9
8
REX
15-speed selection (combination with three speeds RL, RM,
RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
10
X10
Inverter run enable signal (FR-HC, FR-CV connection)
Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
14
X14
PID control valid terminal
Pr. 127 to Pr. 134
15
BRI
Brake opening completion signal
Pr. 278 to Pr. 283
16
X16
PU-External operation switchover (turning ON X16 selects
External operation)
Pr. 79, Pr. 340
18
X18
V/F switchover (V/F control is performed when X18 is ON)
Pr. 80, Pr. 81, Pr. 800
,
24
MRS
Output stop
Pr. 17
25
STOP
Start self-holding selection
—
60
STF
Forward rotation command (assigned to STF terminal
(Pr. 178)
only)
—
61
STR
Reverse rotation command (assigned to STR terminal
(Pr. 179)
only)
—
62
RES
Inverter reset
—
—
65
X65
PU/NET operation switchover (turning ON X65 selects PU
operation)
Pr. 79, Pr. 340
66
X66
External/NET operation switchover (turning ON X66 selects
NET operation)
Pr. 79, Pr. 340
67
X67
Command source switchover (turning ON X67 makes
Pr. 338
and Pr. 339
commands valid)
Pr. 338, Pr. 339
9999
—
No function
—
—
NOTE
Changing the terminal assignment using
Pr.178 to Pr.184 (input terminal function selection)
may affect the other functions.
Set parameters after confirming the function of each terminal.
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
The priorities of the speed commands are in order of JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the X10 signal (FR-HC, FR-CV connection-inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned with
Pr.79 Operation mode selection
set to "7", the MRS signal shares this
function.
Same signal is used to assign multi-speed (7 speeds) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same
time.)
Switch the control method using external terminal (X18 signal) during an inverter stop. If control method between V/F
control and Advanced (General-purpose magnetic) flux vector control is switched during the operation, the actual
switchover does not take place until the inverter stops. In addition, if control method is switched to V/F control during
the operation, only second function becomes valid as V/F control and second function are selected simultaneously in
V/F control.
Turning the AU signal ON makes terminal 2 (voltage input) invalid.
Setting
Signal
Function
Related Parameters
Refer to
Page
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...