84
Control mode
4.3.1
Changing the control method (Pr. 80, Pr. 81, Pr. 800)
∗
Set a value other than "9999" in
Pr. 80
and
Pr. 81
.
(1) Setting of the motor capacity and the number of motor poles
(Pr. 80, Pr. 81)
Motor specifications (motor capacity and number of motor poles) must be set to select Advanced magnetic flux vector
control or General-purpose magnetic flux vector control.
Set the motor capacity (kW) in
Pr. 80
Motor capacity
and set the number of motor poles in
Pr. 81
Number of motor poles
.
(2) Selection of control method
Select the inverter control method for V/F control, Advanced magnetic flux vector control, and General-purpose magnetic
flux vector control.
∗
Control method is V/F control regardless of the setting value of
Pr. 800
when "9999" is set in
Pr. 80
Motor capacity
or
Pr. 81
Number of motor poles
.
(3) Control method switching by external terminals (X18 signal)
Use the V/F switchover signal (X18) to change the control method (between V/F control and Advanced magnetic flux
vector control (General-purpose magnetic flux vector control)) with external terminal.
Turn the X18 signal ON to change the currently selected control method (Advanced magnetic flux vector control or
General-purpose magnetic flux vector control) to V/F control.
For the terminal used for X18 signal input, set "18" in any of
Pr. 178
to
Pr. 184
(input terminal function selection)
to assign the
function.
Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux
vector control. The initial value is V/F control.
Select a control mode using
Pr.
800 Control method selection
.
Parameter
Number
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
0.1 to 15kW
Set the applied motor capacity.
9999
V/F Control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
9999
V/F Control
800
Control method
selection
20
20
V/F
Control
Advanced magnetic flux vector control
∗
30
General-purpose magnetic flux vector control
∗
Pr. 80, 81
Pr. 800
Setting
Control Method
Other than 9999
20
(
Pr. 800
initial value)
Advanced magnetic flux vector control
30
General-purpose magnetic flux vector control
9999
(
Pr. 80, Pr. 81
initial value)
—
∗
V/F control
REMARKS
Switch the control method using external terminal (X18 signal) during an inverter stop. If control method between V/F control and
Advanced (General-purpose) magnetic flux vector control is switched during the operation, the actual switchover does not take
place until the inverter stops. In addition, if control method is switched to V/F control during the operation, only second function
becomes valid as V/F control and second function are selected simultaneously in V/F control.
NOTE
Changing the terminal assignment using
Pr.
178 to Pr. 184 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Advanced magnetic flux vector control
General-purpose magnetic flux vector control
Pr. 178 to Pr. 184 (input terminal function selection)
Pr. 450 Second applied motor
Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 46 Second torque boost
Pr. 47 Second V/F (base frequency)
Pr. 48 Second stall prevention operation current
Pr. 51 Second electronic thermal O/L relay
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...