39
EMC and leakage currents
3.1.4
Harmonic suppression guideline in Japan
Harmonic currents flow from the drive unit to a power receiving point via a power transformer. The harmonic suppression
guideline was established to protect other consumers from these outgoing harmonic currents.
"Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially high-voltage
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values are exceeded, this
guideline requires the consumer to take certain suppression measures.
(1) Application for specific consumers
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power Voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Table 2 Conversion Factors for FR-E700EX Series
Class
Circuit Type
Conversion Factor (Ki)
3
Three-phase bridge
(Capacitor smoothing)
Without reactor
K31 = 3.4
With reactor (AC side)
K32 = 1.8
With reactor (DC side)
K33 = 1.8
With reactors (AC, DC sides)
K34 = 1.4
5
Self-excitation three-
phase bridge
When high power factor converter is used
K5 = 0
Table 3 Equivalent Capacity Limits
Received Power Voltage
Reference Capacity
6.6kV
50kVA
22/33kV
300kVA
66kV or more
2000kVA
Table 4 Harmonic Contents (Values at the fundamental current of 100%)
Reactor
5th
7th
11th
13th
17th
19th
23rd
25th
Three-phase bridge
(Capacitor
smoothing)
Not used
65
41
8.5
7.7
4.3
3.1
2.6
1.8
Used (AC side)
38
14.5
7.4
3.4
3.2
1.9
1.7
1.3
Used (DC side)
30
13
8.4
5.0
4.7
3.2
3.0
2.2
Used (AC, DC sides)
28
9.1
7.2
4.1
3.2
2.4
1.6
1.4
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equivalent
capacity total
Calculation of outgoing
harmonic current
Not more than
harmonic current upper
limit?
Harmonic suppression
measures unnecessary
Harmonic suppression
measures necessary
Equal to or less
than upper limit
More than upper limit
Above reference
capacity
Equal to or less
than reference
capacity
Содержание FR-E700EX
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 288: ...286 MEMO ...
Страница 302: ...300 MEMO ...
Страница 314: ...312 MEMO ...
Страница 315: ...313 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...