105
Selection and protection of a motor
4.9.2
Applied motor (Pr.71)
........Specifications differ according to the date assembled.
to check the SERIAL number.
4.9.3
Offline auto tuning (Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, Pr.90, Pr.92, Pr.93, Pr.96,
Pr.672, Pr.702, Pr.706, Pr.707, Pr.711, Pr.712, Pr.717, Pr.721, Pr.724 to Pr.726, Pr.859)
Set the applied motor type.
When the S-PM geared motor is used, the motor type is automatically set by PM parameter initialization.
Parameter
Number
Name
Initial Value
Setting Range
Description
71
Applied motor
1040
1040
S-PM geared motor
8090
IPM motor
9090
SPM motor
NOTE
When the applied motor is not S-PM geared motor offline auto tuning is required by setting
Pr.96 Auto tuning setting/
status
. (For the details on offline auto tuning,
When the S-PM geared motor is not used, offline auto tuning is required.
• What is offline auto tuning?
This function simplifies setting of parameters for driving PM motors. The motor constants used for operation under
PM sensorless vector control are measured automatically. (Some motors cannot be driven with the result of offline
auto tuning.)
Parameter
Number
Name
Initial Value
Setting Range
Description
9
Electronic thermal O/L
relay
Rated motor
current
0 to 500A
Set the rated motor current.
71
Applied motor
1040
8090
IPM motor
9090
SPM motor
1040
S-PM geared motor
80
Motor capacity
Motor capacity
0.01 to 3.7kW
Set the applied motor capacity.
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
9999
As the internal data of the drive unit is used,
set it correctly according to the motor
specifications.
83
Rated motor voltage
200V / 400V
0 to 1000V
Set the rated motor voltage (V).
84
Rated motor speed
9999
300 to 6000r/min /
200 to 4000r/min
Set the rated motor speed (r/min).
9999
As the internal data of the drive unit is used,
set it correctly according to the motor
specifications.
90
Motor constant (R1)
9999
0 to 50
, 9999
Tuning data
(The value measured by offline auto tuning
is automatically set.)
9999: Internal data of the drive unit is used.
92
Motor constant (Ld)
9999
0 to 500mH, 9999
93
Motor constant (Lq)
9999
0 to 500mH, 9999
96
Auto tuning setting/status
0
0
No offline auto tuning
1
Perform offline auto tuning.
672
Lq tuning target current
adjustment coefficient
9999
50 to 150%
Adjust the target current during tuning.
9999
100%
702
Maximum motor speed
9999
0 to 6000r/min /
0 to 4000r/min
Set the permissible speed (frequency) of the
motor.
9999
The
Pr.84
setting is used.