6.5 Resolver position tuning
• Resolver position tuning is required when a PM motor with a resolver is driven. The measured offset value between the
motor home magnetic pole position and the resolver home position is stored. Only the resolver position tuning can be
performed when offline auto tuning is not required, such as when the parameters for motor constant are set manually, or
when offline auto tuning is already performed.
Before performing resolver position tuning
• Check that the FR-A8APR, a motor, and a resolver are properly connected.
• Check that a motor (single, stop status) is connected. (Check that the motor is not rotated by an external force during
tuning.)
• Check that the mechanical brake is released.
• Check that the vector control (speed control) for the PM motor with a resolver is selected (refer to
NOTE
• The resolver position tuning is required when a PM motor is used. (It is disabled when an induction motor is used.)
• When auto tuning is performed at the setting of
Pr.96
="101", offline auto tuning and the resolver position tuning can be
performed at the same time (refer to
).
Setting
• To perform tuning, set
Pr.373
="1".
Pr.
Name
Initial
value
Setting
range
Description
373
C142
Resolver position tuning setting/status
0
0
Resolver position tuning disabled
1
Resolver position tuning enabled
1105
C143
Resolver magnetic pole position offset
9999
0 to 4095
Resolver position tuning result is set.
9999
Resolver position tuning not performed
Vector
Vector
Vector