24
4
4.5
Output Signal List (FR-E700 series)
For details of signal definitions, refer to
Pr. 190 to Pr. 192 (Output terminal function selection)
of the inverter
(FR-E700 series) manual.
*1
These parameters can be set only in the safety stop function model.
Setting
Signal
Name
Function
Positive
logic
0
RUN
Inverter running
1
SU
Up to frequency
3
OL
Overload alarm
4
FU
Output frequency detection
7
RBP
Regenerative brake pre-alarm
8
THP
Electronic thermal O/L relay pre-alarm
11
RY
Inverter operation ready
12
Y12
Output current detection
13
Y13
Zero current detection
14
FDN
PID lower limit
15
FUP
PID upper limit
16
RL
PID forward/reverse rotation output
20
BOF
Brake opening request
25
FAN
Fan fault output
26
FIN
Heatsink overheat pre-alarm
46
Y46
During deceleration at occurrence of
power failure (retained until release)
47
PID
During PID control activated
64
Y64
During retry
80
SAFE Safety monitor output
81
SAFE2 Safety monitor output 2
90
Y90
Life alarm
91
Y91
Fault output 3 (power-off signal)
95
Y95
Maintenance timer signal
96
REM
Remote output
98
LF
Alarm output
99
ALM
Fault output
9999
No function
Setting
Signal
Name
Function
Positive
logic
REMARKS
• Negative logic can not be set.