6
SPECIFICATIONS
3
Model name (Service Ref.)
EHSE-YM9EC.UK
EHSE-MEC.UK
ERSE-YM9EC.UK
ERSE-MEC.UK
Overall unit dimensions
950 × 600 × 360 mm (Height × Width × Depth)
Weight (empty)
62 kg
60 kg
63 kg
61 kg
Weight (full)
72 kg
70 kg
73 kg
71 kg
Water volume of heating circuit in the unit
10 kg
Cooling mode
NOT available
Available
Unvented expansion
vessel(Primary heating)
Nominal volume
—
Charge pressure
—
Safety
device
Water
circuit
(Primary)
Control thermistor
1–80°C
Pressure relief valve
0.3 MPa (3bar)
Flow sensor
Min. flow 5.0 L/min
Booster
heater
Manual reset thermostat
90°C
—
90°C
—
Thermal Cut-out (for dry run prevention)
121°C
—
121°C
—
Primary circuit circulating Pump
Grundfos UPMXL GE0 25 - 125 180PWM
Connections
Water
G1-1/2
Refrigerant (R410A)
Liquid
3/8 F
Gas
3/4 F
Target temperature
range
Flow temperature
Heating
25–60°C
Cooling
—
5–25°C
Room temperature
Heating
10–30°C
Cooling
—
NOT available
Guaranteed operating
range
Ambient *
1
0–35°C (
80%RH)
Outdoor temperature
Heating
See outdoor unit spec table.
Cooling
—
See outdoor unit spec table
(min. 10°C). *
2
Electrical data
Control board
Power supply
(Phase, voltage, frequency)
~/N, 230 V, 50 Hz
Breaker (when powered
from independent source)
10 A
Booster heater
Power supply
(Phase, voltage, frequency)
3~, 400 V,
50 Hz
—
3~, 400 V,
50 Hz
—
Capacity
3 kW+6 kW
—
3 kW+6 kW
—
Current
13 A
—
13 A
—
Breaker
16 A
—
16 A
—
Sound level
30 dB(A)
Optional extras
● Wireless Remote Controller
PAR-WT50R-E
● Tank thermistor (THW5) (30 m)
PAC-TH011TKL-E
● Wireless Receiver
PAR-WR51R-E
● Thermistor
PAC-TH011-E
● Remote Sensor
PAC-SE41TS-E
● High temperature thermistor
PAC-TH011HT-E
● Tank thermistor (THW5) (5 m) PAC-TH011TK-E
● ecodan Wi-Fi Interface
PAC-WF010-E
● Joint pipe
MAC-A454JP-E
*1 The environment must be frost-free.
*2 Cooling mode is not available in low outdoor temperature.
If you use our system in cooling mode at the low ambient temperature (10°C or below), there are some risks of plate heat exchanger breaking by frozen water.
OCH590B