30
<Running information>
This function shows current temperature and other data of main component parts
of both the indoor and outdoor units.
1. From the Service menu highlight Running information.
2. Press CONFIRM.
3. Press F3 and F4 buttons to set the Ref. address. *
1
4. Use the function buttons to enter index code for the component to be viewed.
(See the Table 9-4-1 for component index codes.)
5. Press CONFIRM.
*
1
For multiple outdoor units control system only.
<Thermistor reading>
This function shows the current readings of thermistors located on the water and refrigerant circuit.
Thermistor Description
Thermistor Description
TH1A
Zone1 room temperature
THW6
Zone1 flow water temperature
TH1B
Zone2 room temperature
THW7
Zone1 return water temperature
TH2
Refrigerant return temperature
THW8
Zone2 flow water temperature
THW1
Water flow temperature
THW9
Zone2 return water temperature
THW2
Water return temperature
THWB1
Boiler flow water temperature
THW5
DHW tank water temperature
THWB2
Boiler return water temperature
TH7
Ambient (outdoor) temperature
External input settings menu screen
Demand control screen
Outdoor thermostat setting screen
<External input settings>
Demand control(IN4)
Outdoor thermostat (IN5)
The selection of “OFF”, whilst a signal is being sent to IN4, forcefully stops all
the heat source operations and the selection of “Boiler” stops operations of
heat pump and electric heater and performs boiler operation.
The selection of “Heater”, whilst a signal is being sent to IN5, performs
electric-heater-only operation and the selection of “Boiler” performs boiler
operation.
OCH590B