S1
S2
S3
L
N
BLACK
BLACK
YELLOW
YELLOW
CNO1
CNO1
Black
Cylinder unit
control board
FTC3 powered
via outdoor unit.
L
N
YELLOW
YELLOW
BLACK
BLACK
CNO1
CNO1
Black
Cylinder unit
control board
S1
S2
S3
FTC3 powered
from independednt
source.
49
10-5. Troubleshooting by inferior phenomena
No.
Fault symptom
Possible cause
Explanation - Solution
1
Main controller display
does not work.
1.
There is no power supply to main controller.
1.
Check LED on FTC3.
(i) When LED2 is lit.
Check the main controller wiring for damage or contact failure.
(ii) When LED2 is blinking.
Refer to No.5 below.
(iii) When LED2 is not lit.
Refer to No.4 below.
.
Power is supplied to main controller,
however, the display on the main controller
is not visible.
.
Check the following.
• Failure of main controller if “ Please Wait” is not displayed.
• Refer to No.2 below if “Please Wait” is displayed.
“Please Wait” remains
displayed on the main
controller.
1.
"Please Wait" is displayed for up to 6 mins.
1.
Normal operation.
.
Communication failure between the main
controller and FTC3.
, 3. Main controller start up checks/procedure.
(i) If main controller - FTC3 can not communicate the number displayed
under "Please Wait" is 0%, or 50-99%.
• Check wiring connections on main controller
• Replace main controller or FTC3 boards.
(ii) If 1-49% is displayed there is a communication errorbetween the outdoor
unit's and FTC3's boards.
• Check the wiring connections on the outdoor unit and FTC3 boards.
(Ensure S1, S2 are not cross wired and S3 is securely connected and not
damaged.)
• Replace the outdoor unit's and/or the FTC3's boards.
3.
Communication failure between FTC3 and
outdoor unit.
3
When pressing the
"ON" button, the main
screen is shown briefly
then disappears.
If whilst changing the settings in the service
menu, the system is shut down.
When you return to the main screen you may have
to wait a short while before the "ON" button will work.
Normal operation.
The unit is processing the recent service menu changes and will be operational
shortly.
4
LED on FTC3 is off.
When LED1 on FTC3 is also off.
<FTC3 powered via outdoor unit.>
1.
Power supply of rated voltage is not supplied
to outdoor unit.
1.
Check the voltage of outdoor power supply terminal block (L,N) or (L3,N).
• When AC220~240V is not detected, check the power wiring to outdoor
unit and the breaker.
• When AC 220~240V is detected, check 2 (below).
. Defective outdoor controller circuit board.
.
Check the voltage between outdoor terminal block S1 and S2.
• When AC 0~40V is not detected, check the fuse on outdoor controller
circuit board, check the wiring connection.
• When AC 220~240V is detected, check 3 (below).
3.
Power supply of AC 220~240V is not
supplied to FTC3.
3.
Check the voltage between indoor terminal block S1 and S2.
• When AC 220~240V is not detected, check FTC3/outdoor unit connecting
wire for miswiring.
• When AC 220~240V is detected, check 4 (below).
4.
Defective FTC3.
4. Check the fuse on FTC3.
• Check the wiring conection.
If no problems are found, FTC3 board is defective.
5.
There are problems in the method of
connecting the connectors.
5.
Check that there is no problem in the method of connecting the connectors.
• When there are problems in the method of connecting the connectors,
connect the connector correctly referring to below.
<FTC3 powered from independent source>
1.
Power supply of AC 220~240V is not
supplied to FTC3.
1.
Check the voltage of indoor power supply terminal block (L,N).
• When AC220~240V is not detected, check the power supply wiring.
• When AC220~240V is detected, check 2 (below).
. There are problems in the method of
connecting the connectors.
.
Check that there is no problem in the method of connecting the connectors.
• When there are problems in the method of connecting the connectors,
connect the connector correctly referring to below.
• When there is no problem in the method of connecting the connectors,
check 3 (below).
3.
Defective FTC3.
3. Check the fuse on FTC3.
• Check the wiring connection.
If no problems are found, FTC3 board is defective.
When LED1 on FTC3 is lit.
Recheck the refrigerant address setting on the outdoor unit.
Set the refrigerant address to “0”.
(Set refrigerant address using SW1(3~6) on outdoor controller circuit board.)
Miss-setting of refrigerant address for
outdoor unit.
(None of the refrigerant address is set to "0".)
Содержание EHPT20X-VM2HA
Страница 11: ... See Chapter 6 10 11 6 WIRING DIAGRAM 6 1 EHST20C VM6HA ...
Страница 12: ... See Chapter 6 10 12 6 2 EHST20C YM9HA ...
Страница 13: ... See Chapter 6 10 13 6 3 EHST20C VM6A EHST20C VM6SA ...
Страница 14: ... See Chapter 6 10 14 6 4 EHST20C YM9A ...
Страница 15: ... See Chapter 6 10 15 6 5 EHPT20X VM2HA ...
Страница 16: ... See Chapter 6 10 16 6 6 EHPT20X VM6HA ...
Страница 17: ... See Chapter 6 10 17 6 7 EHPT20X YM9HA ...
Страница 18: ... See Chapter 6 10 18 6 8 EHPT20X VM6A ...
Страница 19: ... See Chapter 6 10 19 6 9 EHPT20X YM9A ...
Страница 25: ...25 WATER SYSTEM DIAGRAM 8 EHST20C M HA M A EHST20C VM6SA ...
Страница 26: ...26 EHPT20X VM2HA EHPT20X M HA M A ...
Страница 75: ...75 ...