OK
NG
NG
Flow switch
Flow switch
Flow switch
Pipe
Pipe
Pipe
Lead wire
Flow
Flow
Flow
61
7. How to remove the flow switch
(1) Remove the front panel. (Refer to Procedure 1.)
(2) Remove the control box cover. (Refer to Procedure 3.)
(3) Disconnect the CN2F connector on the controller board.
(Photo 4-1)
(4) Release the lead wire from the 5 bands and 2 cable
straps. (Photos 10-1, 10-2)
(5) Close (OFF) the strainer valve handle (under).
(Photo 10-2)
w
When the valve handle is stiff, remove the handle and
turn the vertical stem 90 degree mainly by using a span
-
ner. (Photo 5-2)
(6) Remove the flow switch by loosening the nut. (Photo 7-1)
w
When reinstalling the flow switch, use a new O-ring.
(Photo 7-2)
Note: To ensure the correct functioning of the flow switch,
check the following when installing it:
▪ The flow switch paddle is set perpendicularly to the
water flow. (Photos 7-2)
▪ The lead wire of the flow switch points toward the left-
hand. (Photo 7-1)
▪ The lead wire runs parallel to the water pipe.
(Figure 7-1)
Photo 7-1
Photo 7-2
Figure 7-1
DISASSEMBLY PROCEDURE
PHOTOS
Nut
Flow switch
Flow direction
Flow switch paddle
O-Ring
Lead wire
Содержание EHPT20X-VM2HA
Страница 11: ... See Chapter 6 10 11 6 WIRING DIAGRAM 6 1 EHST20C VM6HA ...
Страница 12: ... See Chapter 6 10 12 6 2 EHST20C YM9HA ...
Страница 13: ... See Chapter 6 10 13 6 3 EHST20C VM6A EHST20C VM6SA ...
Страница 14: ... See Chapter 6 10 14 6 4 EHST20C YM9A ...
Страница 15: ... See Chapter 6 10 15 6 5 EHPT20X VM2HA ...
Страница 16: ... See Chapter 6 10 16 6 6 EHPT20X VM6HA ...
Страница 17: ... See Chapter 6 10 17 6 7 EHPT20X YM9HA ...
Страница 18: ... See Chapter 6 10 18 6 8 EHPT20X VM6A ...
Страница 19: ... See Chapter 6 10 19 6 9 EHPT20X YM9A ...
Страница 25: ...25 WATER SYSTEM DIAGRAM 8 EHST20C M HA M A EHST20C VM6SA ...
Страница 26: ...26 EHPT20X VM2HA EHPT20X M HA M A ...
Страница 75: ...75 ...