INSTALLATION: FTC2
HEATER SETTING
Set Dip SW1-4 according to whether the system has an Immersion
heater.
Set Dip SW1-5 according to the location of Booster heater.
Summary: Heater setting
SW 1-4
Setting
OFF
Without immersion heater
ON
With immersion heater
SW 1-5
Setting
OFF
For both domestic hot water and heating
ON
For heating only or without booster heater
SW 1-4
Immersion heater
SW 1-5
Booster heater position
Diagram
OFF
(without immersion heater)
OFF
(For both DHW and heating)
ON
(with immersion heater)
OFF
(For both DHW and heating)
OFF
(without immersion heater)
ON
(For heating only)
ON
(with immersion heater)
ON
(for heating only)
Table 2.1
Table 2.2
Table 2.3
SW 1-3 Setting
Notes
OFF
With DHW tank
Necessary to connect TH5
ON
Without DHW tank
NOT necessary to connect TH5
SW 1-6 Setting
Notes
ON
Packaged type
NOT necessary to connect TH5
Table 2.5
THERMISTOR SETTING
Set Dip SW 1-3 according to whether the system has a domestic hot water tank. When Dip SW 1-3 is ON, domestic hot water
mode is NOT available Set Dip SW1-6 according to the Ecodan type.
Table 2.4
34