DISASSEMBLY PROCEDURE
PHOTOS
76
77
Photo 10-1
10. How to remove the plate heat exchanger
(1) Remove the front panel. (Refer to Procedure 1.)
(2) Pump down the refrigerant circuit and close the
stop valve at the outdoor unit side. (Refer to 1.
SUPPLEMENTARY INFORMATION.)
(3) Remove the control box. (Refer to Procedure 4.)
(4) Cut the bands and remove the pump frame. (Photo 10-1)
(5) Cut the bands bundling the pipes. (Photos 10-2, 10-3)
(6) Remove the 2 flare nuts on the refrigerant piping on top
of the cylinder unit. (Photo 10-)
(7)
Close (OFF) the strainer valve handle (under).
w
When the valve handle is stiff, remove the handle and
turn the vertical stem 90 degree mainly by using a
spanner. (Photo 5-)
(8) Remove the G1" nut at the booster heater side of the
flexible hose. (Photo 10-2)
w
When reinstalling the G1" nut, use a new G1" gasket.
(9)
Remove the G1" nut under the strainer valve. (Photo 10-2)
w
When reinstalling the G1" nut, use a new G1" gasket.
(10) Remove the 4 screws fixing the plate heat exchanger.
(Photo 10-)
Photo 10-2
Photo 10-3
Pump frame
Screw
Screws
Nut (G1")
(under the strainer valve)
Flare nuts
Nut (G1")
Bands
Screws
Bands
Bands
Band
Top panel
Strainer
valve
Plate heat
exchanger
Screw
Gasket (G1")
Strainer
valve handle
(under)
Band
Gasket (G1")
Fastener
OCH531
Содержание ecodan EHPT20X- VM2HB