![Mitsubishi Electric E1070 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/mitsubishi-electric/e1070/e1070_installation-manual_238475013.webp)
Technical Data
Mitsubishi Electric, MA00776C
13
3
Technical Data
Parameter
E1070
Front panel, W x H x D 285 x 177 x 6 mm
Mounting depth
56 mm (156 mm including clearance)
Front panel seal
IP 66
Rear panel seal
IP 20
Keyboard material
Membrane switch keyboard with metal domes. Overlay film
of Autotex F157 * with print on reverse side. 1 million
operations.
Reverse side material
Powder-coated aluminum
Weight
1.4 kg
Serial port RS422/
RS485
25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC.
Serial port RS232C
9-pin D-sub contact, male with standard locking screws 4-40
UNC.
Ethernet
Shielded RJ 45
USB
Host type A (USB 1.1), max output current 500mA
Device type B (USB 1.1)
CF-slot
Compact flash, type I and II
Flash memory for
application
12 MB (incl. fonts)
Real time clock
±20 PPM + error because of ambient temperature and supply
voltage. Total maximum error: 1 min/month at 25
°
C
Temperature coefficient: 0.004 ppm/
°
C
2
Real time clock
battery
CR2450 (UL and cUL: Sanyo or Panasonic)
Minimum lifetime: 3 years
Power consumption at
rated voltage
Normal: 0.4 A
Maximum: 0.9 A
Display
TFT-LCD. 640 x 480 pixels, 64K color.
CCFL backlight lifetime at the ambient temperature of
+25
°
C: >50,000 h.
Active area of display,
W x H
131.5 x 98.6 mm
Fuse
Internal DC fuse, 3.15 AT, 5 x 20 mm
Power supply
+24V DC (20 - 30V DC). Power supply connector.
CE: The power supply must conform with the requirements
according to IEC 60950 and IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class II power supplies.
Ambient temperature
Vertical installation: 0
°
to +50
°
C
Horizontal installation: 0
°
to +40
°
C
Storage temperature
-20
°
to +70
°
C
Relative humidity
5 - 85 % non-condensed
CE approvals
Noise tested according to EN61000-6-4 emission and
EN61000-6-2 immunity.
UL, cUL approvals
(when procuct or
packing is marked)
UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only
DNV
Yes
NEMA
4x indoor use only
* See section
for more information.
Содержание E1070
Страница 1: ...MITSUBISHI ELECTRIC E1070 Installation manual MA00776C 2008 07 English ...
Страница 4: ...Table of Contents Mitsubishi Electric MA00776C ...
Страница 8: ...Safety Precautions 8 Mitsubishi Electric MA00776C ...
Страница 12: ...Installation 12 Mitsubishi Electric MA00776C ...
Страница 14: ...Technical Data 14 Mitsubishi Electric MA00776C ...
Страница 18: ...Operator Panel Drawings 18 Mitsubishi Electric MA00776C 5 2 E1070 Outline Drawing No S 5031 Date 2004 10 14 ...
Страница 19: ...Operator Panel Drawings Mitsubishi Electric MA00776C 19 5 3 E1070 Text Strip Drawing No S 5027 Date 2004 08 12 ...
Страница 20: ...Operator Panel Drawings 20 Mitsubishi Electric MA00776C ...