GB-38
WT08432X01
(2) Units "ft" and "oz" (In an R2 system)
<Formula>
・
When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
additional
charge (oz)
=
High-pressure pipe
ø1-3/8 total length
× 6.24 (oz/ft)
+
High-pressure pipe
ø1-1/8 total length
× 3.88 (oz/ft)
+
High-pressure pipe
ø7/8 total length
× 2.48 (oz/ft)
+
High-pressure pipe
ø3/4 total length
× 1.73 (oz/ft)
+
High-pressure pipe
ø5/8 total length
× 1.19 (oz/ft)
+
Liquid pipe ø3/4
total length
× 3.12 (oz/ft)
+
Liquid pipe ø5/8
total length
× 2.16 (oz/ft)
+
Liquid pipe ø1/2
total length
× 1.30 (oz/ft)
+
Liquid pipe ø3/8
total length
× 0.65 (oz/ft)
+
Liquid pipe ø1/4
total length
× 0.26 (oz/ft)
+
Main or sub BC
controller
Amount (oz/unit)
+
Total capacity of connected
indoor units
Amount (oz)
(to be added for
indoor unit)
J-type
53
80 or below
71
JA-type
106
81 to 160
89
KA-type
166
161 to 330
106
KB-type
15
331 to 390
124
391 to 480
159
481 to 630
177
631 to 710
212
711 to 800
283
801 to 890
318
891 to 1070
353
1071 to 1250
424
1251 or above
494
* When connecting PEFY-P50VMHS2-E, add 100 oz of refrigerant per indoor unit.
* When connecting PEFY-P63VMHS2-E, add 116 oz of refrigerant per indoor unit.
* When connecting PEFY-P71VMHS2-E, add 89 oz of refrigerant per indoor unit.
* When connecting PEFY-P80VMHS2-E, add 89 oz of refrigerant per indoor unit.
* When connecting PEFY-P100VMHS2-E, add 89 oz of refrigerant per indoor unit.
* Contact your dealer for the amount of refrigerant to be added when connecting CMB-P**-V-G1, CMB-P**-V-GA1, CMB-P**-V-HA1, CMB-P**-
V-GB1, or CMB-P**-V-HB1.
* When connecting LEV kit (PAC-LV11M-J), additional refrigerant charge may be required. Contact your dealer for details.
・
When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
additional
charge (oz)
=
High-pressure pipe
ø1-3/8 total length
× 5.60 (oz/ft)
+
High-pressure pipe
ø1-1/8 total length
× 3.54 (oz/ft)
+
High-pressure pipe
ø7/8 total length
× 2.26 (oz/ft)
+
High-pressure pipe
ø3/4 total length
× 1.51 (oz/ft)
+
High-pressure pipe
ø5/8 total length
× 1.08 (oz/ft)
+
Liquid pipe ø3/4
total length
× 2.80 (oz/ft)
+
Liquid pipe ø5/8
total length
× 1.94 (oz/ft)
+
Liquid pipe ø1/2
total length
× 1.19 (oz/ft)
+
Liquid pipe ø3/8
total length
× 0.59 (oz/ft)
+
Liquid pipe ø1/4
total length
× 0.23 (oz/ft)
+
Main or sub BC
controller
Amount (oz/unit)
+
Total capacity of connected
indoor units
Amount (oz)
(to be added for
indoor unit)
J-type
53
80 or below
71
JA-type
106
81 to 160
89
KA-type
166
161 to 330
106
KB-type
15
331 to 390
124
391 to 480
159
481 to 630
177
631 to 710
212
711 to 800
283
801 to 890
318
891 to 1070
353
1071 to 1250
424
1251 or above
494
* When connecting PEFY-P50VMHS2-E, add 100 oz of refrigerant per indoor unit.
* When connecting PEFY-P63VMHS2-E, add 116 oz of refrigerant per indoor unit.
* When connecting PEFY-P71VMHS2-E, add 89 oz of refrigerant per indoor unit.
* When connecting PEFY-P80VMHS2-E, add 89 oz of refrigerant per indoor unit.
* When connecting PEFY-P100VMHS2-E, add 89 oz of refrigerant per indoor unit.
* Contact your dealer for the amount of refrigerant to be added when connecting CMB-P**-V-G1, CMB-P**-V-GA1, CMB-P**-V-HA1, CMB-P**-
V-GB1, or CMB-P**-V-HB1.
* When connecting LEV kit (PAC-LV11M-J), additional refrigerant charge may be required. Contact your dealer for details.