GB-34
WT08432X01
9-8. Evacuation of the system
Do not purge the air using refrigerant. Use a vacuum pump to evacuate the system.
- Residual gas in the refrigerant lines will cause bursting of the pipes or an explosion.
Use a vacuum pump with a check valve.
- If the vacuum pump oil flows back into the refrigerant lines, the refrigerant oil may deteriorate
and the compressor may malfunction.
<Evacuation procedures>
①
Evacuate the system from both service ports, using a vacuum pump with the service valves closed.
②
After the vacuum reaches 650 Pa, continue evacuation for at least one hour.
③
Stop the vacuum pump and leave it for an hour.
④
Verify that the vacuum has not increased by more than 130 Pa.
⑤
If the vacuum has increased by more than 130 Pa, water infiltration is suspected. Pressurize the system with dry
nitrogen gas up to 0.05 MPa. Repeat
①
though
⑤
until the vacuum is increased by 130 Pa or below. If the
results persist, then perform the "Triple Evacuation" below.
<Triple Evacuation>
①
Evacuate the system to 533 Pa from both service ports, using a vacuum pump.
②
Pressurize the system with dry nitrogen gas up to 0 Pa from the discharge service port.
③
Evacuate the system to 200 Pa from the suction service port, using a vacuum pump.
④
Pressurize the system with dry nitrogen gas up to 0 Pa from the discharge service port.
⑤
Evacuate the system from both service ports, using a vacuum pump.
⑥
After the vacuum reaches 66.7 Pa, stop the vacuum pump and leave it for an hour. A vacuum of 66.7 Pa must
be maintained for at least one hour.
⑦
Verify that the vacuum has not increased for at least 30 minutes.
LO
HI
Ⓐ
Ⓑ
Ⓒ
Ⓝ
Ⓝ
Ⓔ
Ⓓ
Ⓕ
Ⓞ
Ⓖ
Ⓗ
Ⓘ
Ⓚ
Ⓙ
Ⓛ
Ⓜ
Ⓐ
Gauge manifold
Ⓑ
Low pressure knob
Ⓒ
High pressure knob
Ⓓ
Service valve
Ⓔ
Low-pressure pipe
Ⓕ
High-pressure pipe
Ⓖ
Service port
Ⓗ
Three-way joint
Ⓘ
Valve (vacuum pump)
Ⓙ
Valve (for charging refrigerant)
Ⓚ
Refrigerant tank
Ⓛ
Scale
Ⓜ
Vacuum pump
Ⓝ
To indoor unit
Ⓞ
Outdoor unit
・
Use a scale that can measure down to 0.1 kg (0.1 oz).
・
Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum Gauge or Micron Gauge
・
Do not use a gauge manifold to measure the vacuum pressure.
・
Use a vacuum pump capable of attaining a vacuum of 65 Pa (abs) within five minutes of operation.
Содержание City Multi R2 Series
Страница 2: ......
Страница 62: ...GB 60 WT08432X01 ...