8. CAPACITY TABLES
Hyper Heating Inverter R2-Series
n: Total number of the indoor units
k: Number of the indoor unit
c
k
: Outdoor unit power input coefficient of k indoor unit room temp.
M
k
: Number part of the k indoor unit model (e.g. P36 → 36)
<Heating>
(1) Rated power input of outdoor unit
5.48 kW (Nominal)
0.94
0.80
(2) Calculation of the average indoor temperature power input coefficient
Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 2 °CW.B., Indoor temp. 25 °CD.B.)
Maximum System Capacity (CTx) = Total Indoor unit Capacity (CTi), so use the following formula
PIo = Outdoor unit Heating Rated Power Input × Correction Coefficient of Indoor temperature × (CTi/CTo)
= 5.48 × 0.8 × 0.94
= 4.12 kW
0.80
Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp. 2 °CW.B., Indoor temp. 25 °CD.B.)
= 0.8 × 36/(36 + 36) + 0.8 × 36/(36 + 36)
= 0.80
n
k=1
n
k=1
Average indoor temp. power input coefficient (
c
ave
)
= ∑ {c
k
×
(M
k
/ ∑ M
k
)}
(4) Outdoor power input (PIo)
(3) Coefficient of the partial load (CTi/CTo)