1. Safety precautions

1.1. Before installation and electric work

s

Before installing the unit, make sure you read all the “Safety
precautions”.

s

The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the
unit.

Symbols used in the illustrations

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Beware of electric shock. (This symbol is displayed on the main unit label.)

<Color: yellow>

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock,

or fire.

Install the unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.

Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.

Prepare for rain and other moisture and earthquakes and install the unit
at the specified place.
- Improper installation may cause the unit to topple and result in injury.

Always use an filter and other accessories specified by Mitsubishi Elec-
tric.
- Ask an authorized technician to install the accessories. Improper installation

by the user may result in water leakage, electric shock, or fire.

Never repair the unit. If the air conditioner must be repaired, consult the
dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may

result.

If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will

be released.

Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may

result.

Have all electric work done by a licensed electrician according to “Elec-
tric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-

properly, electric shock and fire may result.

Securely install the heat source unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter

the heat source unit and fire or electric shock may result.

When installing and moving the air conditioner to another site, do not
charge the it with a refrigerant different from the refrigerant (R407C) speci-
fied on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-

erant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety

limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.

When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or

fire may result.

After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or

other heat source, it may generate noxious gases.

Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted

and operated forcibly, or parts other than those specified by Mitsubishi Elec-
tric are used, fire or explosion may result.

To dispose of this product, consult your dealer.

The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.

Pay a special attention to the place, such as a basement, etc. where re-
frigeration gas can stay, since refrigeration is heavier than the air.

1.2. Precautions for devices that use R407C

refrigerant

 Caution:

Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large

amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.

Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contami-
nant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant residual oil to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor trouble may result.

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral

oil.

Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system,  the composition of the refriger-

ant in the cylinder will change and performance may drop.

1. Safety precautions ...................................................................................... 5

1.1. Before installation and electric work .......................................... 5
1.2. Precautions for devices that use R407C refrigerant .................. 5
1.3. Before getting installed .............................................................. 6
1.4. Before getting installed (moved) - electrical work ...................... 6
1.5. Before starting the test run ........................................................ 6

2. Specifications .............................................................................................. 6
3. Confirmation of parts attached ................................................................... 6
4. Lifting method and weight of product .......................................................... 7
5. Installation of unit and service space .......................................................... 7

5.1. Installation ................................................................................. 7
5.2. Service space ............................................................................ 7

6. Water pipe installation ................................................................................. 7

6.1. Precautions during installation .................................................. 7
6.2. Insulation installation ................................................................. 7
6.3. Water processing and water quality control ............................... 7
6.4. Pump interlock ........................................................................... 8

7. Refrigerant piping installation ..................................................................... 8

7.1. Caution ...................................................................................... 8
7.2. Refrigerant piping system .......................................................... 8

8. Additional refrigerant charge ....................................................................... 8

8.1. Calculation of Additional Refrigerant Charge ............................ 8
8.2. Caution for piping connection/valve operation ........................... 9
8.3. Airtight test, evacuation, and refrigerant charging ..................... 9
8.4. Thermal insulation of refrigerant piping ................................... 10

9. Wiring ........................................................................................................ 11

9.1. Caution .................................................................................... 11
9.2. Control box and connecting position of wiring ......................... 11
9.3. Wiring transmission cables ...................................................... 11
9.4. Wiring of main power supply and equipment capacity ............ 12

10. Test run ..................................................................................................... 12

10.1. The following phenomena do not represent trouble

(emergency) ............................................................................ 12

Содержание CITY MULTI PQRY-P-YMF-C Series

Страница 1: ...r un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unid...

Страница 2: ...view A Piping space for left piping B Heat source unit C Service space front side D Top view D Anti vibration pad E Concrete base E Piping space for top piping F Piping space for left piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet E Refrigerant piping F Y type strainer G Water inlet H Drain pipe A Short circuit wire Connected before deliv...

Страница 3: ...g f h A BC controller B Indoor unit 20 140 C Indoor unit 200 250 A Valve stem B Stopper pin C Packing Accessory D Connecting pipe Accessory E Open Operate slowly F Cap copper packing G Service port H Flare nut I ø19 05 J ø25 4 PQRY P200 ø28 58 PQRY P250 K Field piping L Close packed packing M Hollow packing A System analyzer B Lo Knob C Hi Knob D Ball valve E Low press pipe F High press pipe G Ser...

Страница 4: ...C 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 53 OC c 1 c4 c 3 BC M1M2S 52 BC M1M2S 54 S Power Supply Unit S MJ103 L3 L 6 L 7 L4 c 3 A B A B A B M1M2 M1M2 c 1 c 1 c2 c2 A B A Steel wire B Piping C Asphaltic oily mastic or aspha...

Страница 5: ...e to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other hea...

Страница 6: ...acuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equipment If the conventional refrigerant and refrigerator...

Страница 7: ...ater inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid valve coil or compressor power supply to become wet Install a back flow prevention valve on the pump and a flexible joint to prevent excess vibration Use a sleeve to protect the pipes where they go through a wall Use metal fittings to secure the pi...

Страница 8: ... circuit connection City Multi R2 Series is constituted by an end branching system in which the refrig erant piping from heat source unit is branched at BC controller and connected to each indoor unit The connection method adapted is flange connection for low pressure pipe and flare connection for high pressure pipe between heat source unit and BC controller and flare connection between BC control...

Страница 9: ...8 3 1 P 3 A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob F Stop valve G Low press pipe H High press pipe I Heat source unit J Service port For R407C models The method of conducting the airtight test is basically the same as for R22 models However since the restrictions have a large affect on deterioration of the refrigera tor oil always observe them Also with nonazeotropic r...

Страница 10: ...el wire Adhesive Heat resistant polyethylene foam Adhesive tape Indoor Vinyl tape Floor exposed Water proof hemp cloth Bronze asphalt Heat source Water proof hemp cloth Zinc plate Oily paint Note When using polyethylene cover as covering material asphalt roofing shall not be required No heat insulation must be provided for electric wires Fig 8 4 2 P 4 A Liquid pipe B Gas pipe C Electric wire D Fin...

Страница 11: ...roller Symbol OC BC IC RC Allowable number of controllers One controller for one OC Two to ten controllers for one OC Maximum of two per group When using shielded wiring connect shield ground of the indoor unit transmis sion line to the earth screw and connect shield ground of the line between heat source units and the central control system transmission line to the shield S terminal of the centra...

Страница 12: ...1 L2 L3 L4 and L1 L2 L3 L5 and L1 L2 L6 L7 500 m 1 25 mm2 or more Max transmission cable length L1 and L3 L4 and L3 L5 and L6 and L2 L6 and L7 200 m 1 25 mm2 or more Remote controller cable length r1 r2 r3 r4 10 m 0 3 to 1 25 mm2 If the length exceeds 10 m use a 1 25 mm2 shielded wire The length of this section L8 should be included in the calculation of the maximum length and overall length 2 MA ...

Страница 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: