10. Test run

10.1. The following phenomena do not represent trouble (emergency)

Display of remote controller

Normal display

“Cooling (heating)” flashes

Normal display

Normal display

Defrost display

No lighting

Heat ready

Normal display

“HO” flashes

Light out

Cause

This is not a trouble as it is just a selecting sound.

When multiple indoor units (max. 3) are connected to the same branch of the BC

controller, the heating (cooling) operation cannot be performed while another

indoor unit is performing a cooling (heating) operation.

Because of the control operation of auto vane, it may change over to horizontal

blow automatically from the downward blow in cooling in case the downward

blow operation has been continued for 1 hour. At defrosting in heating, hot adjust-

ing and thermostat OFF, it automatically changes over to horizontal blow.

Ultra-low speed operation is commenced at thermostat OFF.

Light air automatically changes over to set value by time or piping temperature at

thermostat ON.

The fan is to stop during defrosting.

Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating).

Ultra low-speed operation for 5 minutes after SW ON or until piping temperature

becomes 35

°

C, low speed operation for 2 minutes thereafter, and then set notch

is commenced. (Hot adjust control)

When the heat source unit is being cooled and the refrigerant is resting, warming

up operation is performed for at least 35 minutes to warm the compressor.

During this time, only the fan operates.

System is being driven.

Operate remote controller again after “HO” disappear.

After a stop of cooling operation, unit continues to operate drain pump for three

minutes and then stops it.

Unit continues to operate drain pump if drainage is generated, even during a

stop.

Phenomenon

Indoor unit and BC controller generate sound

at the cooling/heating change over sometime.

Indoor unit does not the perform cooling (heat-

ing) operation.

The auto vane runs freely.

Fan setting changes during heating.

Fan stops during heating operation.

Fan does not stop while operation has been

stopped.

No setting of fan while start SW has been

turned on.

Heat source unit does not operate by turning

switch on.

Indoor unit remote controller shows “HO” in-

dicator for about two minutes when turning

ON universal power supply.

Drain pump does not stop while unit has been

stopped.

Drain pump continues to operate while unit

has been stopped.

<Permissible Lengths>

1

M-NET Remote controller

Max length via heat source units: L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

3

+L

5

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length: L

and L

3

+L

4

 and L

3

+L

5

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m (1.25 mm

2

 or more)

Remote controller cable length:

r

1

r

2

r

3

r

4

  

=

 10 m (0.3 to 1.25 mm

2

)

If the length exceeds 10 m, use a 1.25 mm

2

 shielded wire.  The length of this section (L

8

) should be included in the calculation of the

maximum length and overall length.

2

MA Remote controller

Max length via heat source unit (M-NET cable): L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length (M-NET cable): L

and L

3

+L

4

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m (1.25 mm

or more)

Remote controller cable length:

c

1

 and 

c

1

+

c

2

+

c

3

 and 

c

1

+

c

2

+

c

3

+

c

4  

=

 200 m (0.3 to 1.25 mm

2

)

9.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)

[Fig. 9.4.1] (P.4)

A

Switch (Breakers for Wiring and Current Leakage)

B

Heat source Unit

C

BC Controller

D

Pull Box

E

Indoor Unit

Thickness of Wire for Main Power Supply and On/Off Capacities

1. Use a separate power supply for the heat source unit and indoor unit.
2. Bear in mind ambient conditions(ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.

Make sure the power-supply voltage does not drop more than 10 %.

4. Specific wiring requirements should adhere to the wiring regulations of the reglon.
5. Power supply cords of parts of appliances for heat source use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57).
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.

 Warning:

Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.

Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

 Caution:

Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.

Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction
of unit or fire.

30A 100mA 0.1sec. or less
40A 100mA 0.1sec. or less

20A 30mA 0.1sec. or less

40A
40A

20A

32
40

16

32
40

16

4.0
6.0

1.5

4.0
6.0

1.5

BC controller

Indoor Unit

Main Cable

Switch (A)

Minimum Wire Thickness (mm

2

)

Branch

Capacity

Fuse

Breaker for Current Leakage

Model

Heat source

Unit

P200
P250


1.5

Breaker for

Wiring  (NFB)

Ground

Содержание CITY MULTI PQRY-P-YMF-C Series

Страница 1: ...r un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unid...

Страница 2: ...view A Piping space for left piping B Heat source unit C Service space front side D Top view D Anti vibration pad E Concrete base E Piping space for top piping F Piping space for left piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet E Refrigerant piping F Y type strainer G Water inlet H Drain pipe A Short circuit wire Connected before deliv...

Страница 3: ...g f h A BC controller B Indoor unit 20 140 C Indoor unit 200 250 A Valve stem B Stopper pin C Packing Accessory D Connecting pipe Accessory E Open Operate slowly F Cap copper packing G Service port H Flare nut I ø19 05 J ø25 4 PQRY P200 ø28 58 PQRY P250 K Field piping L Close packed packing M Hollow packing A System analyzer B Lo Knob C Hi Knob D Ball valve E Low press pipe F High press pipe G Ser...

Страница 4: ...C 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 53 OC c 1 c4 c 3 BC M1M2S 52 BC M1M2S 54 S Power Supply Unit S MJ103 L3 L 6 L 7 L4 c 3 A B A B A B M1M2 M1M2 c 1 c 1 c2 c2 A B A Steel wire B Piping C Asphaltic oily mastic or aspha...

Страница 5: ...e to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other hea...

Страница 6: ...acuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equipment If the conventional refrigerant and refrigerator...

Страница 7: ...ater inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid valve coil or compressor power supply to become wet Install a back flow prevention valve on the pump and a flexible joint to prevent excess vibration Use a sleeve to protect the pipes where they go through a wall Use metal fittings to secure the pi...

Страница 8: ... circuit connection City Multi R2 Series is constituted by an end branching system in which the refrig erant piping from heat source unit is branched at BC controller and connected to each indoor unit The connection method adapted is flange connection for low pressure pipe and flare connection for high pressure pipe between heat source unit and BC controller and flare connection between BC control...

Страница 9: ...8 3 1 P 3 A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob F Stop valve G Low press pipe H High press pipe I Heat source unit J Service port For R407C models The method of conducting the airtight test is basically the same as for R22 models However since the restrictions have a large affect on deterioration of the refrigera tor oil always observe them Also with nonazeotropic r...

Страница 10: ...el wire Adhesive Heat resistant polyethylene foam Adhesive tape Indoor Vinyl tape Floor exposed Water proof hemp cloth Bronze asphalt Heat source Water proof hemp cloth Zinc plate Oily paint Note When using polyethylene cover as covering material asphalt roofing shall not be required No heat insulation must be provided for electric wires Fig 8 4 2 P 4 A Liquid pipe B Gas pipe C Electric wire D Fin...

Страница 11: ...roller Symbol OC BC IC RC Allowable number of controllers One controller for one OC Two to ten controllers for one OC Maximum of two per group When using shielded wiring connect shield ground of the indoor unit transmis sion line to the earth screw and connect shield ground of the line between heat source units and the central control system transmission line to the shield S terminal of the centra...

Страница 12: ...1 L2 L3 L4 and L1 L2 L3 L5 and L1 L2 L6 L7 500 m 1 25 mm2 or more Max transmission cable length L1 and L3 L4 and L3 L5 and L6 and L2 L6 and L7 200 m 1 25 mm2 or more Remote controller cable length r1 r2 r3 r4 10 m 0 3 to 1 25 mm2 If the length exceeds 10 m use a 1 25 mm2 shielded wire The length of this section L8 should be included in the calculation of the maximum length and overall length 2 MA ...

Страница 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: