4.5. Setting addresses (Fig. 4-4)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
1
How to set addresses
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match
SW11(for 1 to 9) with “3”.
2
How to set branch numbers SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection
number.
Remain other than series R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
A
Address board
Fig. 4-4
4. Electrical work
4.6. Switch setting for high ceiling or at the time of
changing the number of air outlets (Fig. 4-4)
With this unit, the air
fl
ow rate and fan speed can be adjusted by setting the SWA
and SWB (slide switch). Select a suitable setting from the table below according to
the installation location.
* Make sure the SWA and SWB switch are set, otherwise problems such as not
getting cool/warm may occur.
PLFY-P12-P30NBMU-E
SWA
SWB
1
2
3
Silent
Standard
High ceiling
4
4 direction
2.5 m, 8.2 ft
2.7 m, 8.9 ft
3.5 m, 11.5 ft
3
3 direction
2.7 m, 8.9 ft
3.0 m, 9.8 ft
3.5 m, 11.5 ft
2
2 direction
3.0 m, 9.8 ft
3.3 m, 10.8 ft
3.5 m, 11.5 ft
4.7. Sensing room temperature with the built-in sen-
sor in a remote controller (Fig.4-4)
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air
fl
ow at a time when the heating
thermometer is OFF.
PLFY-P36NBMU-E
SWA
SWB
1
2
3
Silent
Standard
High ceiling
4
4 direction
2.7 m, 8.9 ft
3.2 m, 10.5 ft
4.5 m, 14.8 ft
3
3 direction
3.0 m, 9.8 ft
3.6 m, 11.8 ft
4.5 m, 14.8 ft
2
2 direction
3.3 m, 10.8 ft
4.0 m, 13.1 ft
4.5 m, 14.8 ft
SW14
SW11
SW12
1 2 3 4 5 6 7 8 9 10
ON
OFF
SW1
SWC
CN82
CN43
3
2
SWA
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 12
3
4
5
67
89
AB
C
D
EF
(10ths DIGIT)
(1s DIGIT)
. /
.
(BRANCH No.)
2
3
SWB
4
4.8. Electrical characteristics
Model
Power supply
IFM
Hz
Volts
Voltage range
MCA (A)
Output (kW)
FLA (A)
PLFY-P12,P15,P18,P24,P30NBMU-E
60Hz
208 / 230V
198 to 253V
0.64 / 0.64
0.050 / 0.050
0.51 / 0.51
PLFY-P36NBMU-E
1.25 / 1.25
0.120 / 0.120
1.00 / 1.00
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA) FLA: Full Load Amps
IFM: Indoor Fan Motor Output: Fan motor rated output