Control modes

Control details

1-1. Thermostat function (Function to prevent restarting for  3 minutes)

  

• 

Room temperature    desired temperature -2°F ···Thermo ON 

 • Room temperature    desired temperature         ···Thermo OFF

1. Thermostat
 function

Remarks

2-1. Hot adjust mode
 

The fan controller becomes the hot adjuster mode for the following conditions.

 

    When starting the HEAT operation

 

    When the thermoregulating function changes from OFF to ON.

 

    When release the HEAT defrosting operation

2. Fan 

 

A: Hot adjust mode starts.

 

B: 5 minutes have passed since the condition A or the indoor liquid pipe 

 

temperature turned 95°F or more. 

 

C: 2 minutes have passed since the condition B. (Terminating the hot adjust mode)

A

C

B

[Extra Low]

[Low]

Set fan speed by the remote controller

Hot adjust mode *1

2-2. Residual heat exclusion mode

 

When the condition changes the auxiliary heater ON to OFF (thermostat or

 

operation stop, etc), the indoor fan operates in [Low] mode for 1 minute. 

· This control is   

same for the 
model without 
auxiliary heater.

*1 "STAND BY"

will be displayed 

during the hot 

adjust mode.

To be continued on the next page.

By the remote controller setting (switch of 2 speeds)

Type 

Fan speed notch

[Low], [High]

2 speeds

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

ûFûC

ûFûC

ERROR CODE

AFTER

TIMER

TIME SUN MON TUE WED THU FRI SAT

ON

OFF

Hr

AFTER

FILTER

FUNCTION

ONLY1Hr.

WEEKLY

SIMPLE

AUTO OFF

6-4. HEAT OPERATION

<How to operate>

 Press POWER ON/OFF button.
 Press the operation MODE button to display HEAT.
 Press the TEMP. button to set the desired temperature.

NOTE

: The set temperature changes 2°F when the       or       button is 

pressed one time. Heating 63 to 83°F.

<Display in HEAT operation>
[DEFROST]

The [DEFROST] symbol is only displayed during the defrost operation.

[STANDBY]

The [STANDBY] symbol is only displayed during the hot adjust mode.

OCH518

Содержание City Multi PKFY-P24NKMU-E2

Страница 1: ...L 9 7 TROUBLESHOOTING 14 8 DISASSEMBLY PROCEDURE 21 Indoor unit Model names Service Ref No OCH518 INDOOR UNIT SPLIT TYPE HEAT PUMP AIR CONDITIONERS R22 R410A Note This manual describes only service data of the indoor units RoHS compliant products have G mark on the spec name plate April 2012 PARTS CATALOG OCB518 PKFY P24NKMU E2 PKFY P24NKMU E2 TH PKFY P30NKMU E2 PKFY P30NKMU E2 TH ...

Страница 2: ...AN SPEED display indicates which fan speed has been selected display The vertical direction of air flow is indicated display Blinks when model is selected display display CHECK and TEST RUN display indicate that the unit is being checked or test run display OPERATION MODE display Operation mode display indicates which operation mode is in effect TIMER CONTROL buttons AUTO STOP OFF timer when this ...

Страница 3: ...he indicator shows the direc tion of the outcoming airflow One Hour Only indicator Room Temperature display Shows the room temperature The room temperature display range is 46 102 F The display blinks if the temperature is less than 46 F or 102 F or more Louver display Indicates the action of the swing louver Does not appear if the louver is not running Power On indicator Indicates that the power ...

Страница 4: ... Book PAC YU25HT 1 phase 208 230V 60Hz Cross fin Aluminum fin and copper tube DC motor Direct drive Polyethylene sheet PP honeycomb Fuse LEV R410A R22 CITY MULTI PKFY P24NKMU E2 Plastic MUNSELL 1 0Y 9 2 0 2 7 0 24 000 0 07 0 50 7 9 27 000 0 07 0 50 365 1170 295 14 3 8 46 1 16 11 5 8 21 46 Line flow fan 1 0 0 0 056 20 26 333 433 710 920 43 49 I D 16mm 5 8 ø9 52 ø3 8 ø9 52 ø3 8 ø15 88 ø5 8 ø15 88 ø5...

Страница 5: ...PKFY P24NKMU E2 External static pressure 0Pa Power source 208 230V 60Hz Measured in anechoic room OCTAVE BAND PRESSURE LEVEL dB 0dB 20MPa PKFY P24NKMU E2 TH PKFY P30NKMU E2 TH 39 49 43 49 Sound level dB A Sound level at anechoic room Low High Service Ref Approximate minimum audible limit on continuous noise High speed Low speed 3 3 ft 1m Measurement location 3 3 ft 1m OCTAVE BAND CENTER FREQUENCIE...

Страница 6: ...142 4 29 32 125 4 19 32 117 3 15 16 100 2 15 16 75 1 31 32 50 15 1 8 384 0 13 3 4 349 2 16 15 16 430 5 1 2 12 5 11 1 2 292 10 13 32 264 9 1 32 229 5 8 17 32 217 6 9 16 167 5 3 32 129 5 4 1 8 104 5 3 7 16 87 5 2 15 32 62 5 1 15 32 37 5 1 2 12 5 2 1 8 54 31 32 25 0 12 1 4 311 8 17 32 216 5 13 11 32 339 20 7 8 530 5 7 7 16 189 13 11 32 339 17 11 16 449 2 23 1 32 585 23 1 32 585 A 5 16 7 8 3 1 32 77 2...

Страница 7: ...7 WIRING DIAGRAM 4 PKFY P24NKMU E2 TH PKFY P30NKMU E2 TH OCH518 ...

Страница 8: ...rature thermistor TH21 Gas pipe thermistor 1 TH23 Liquid pipe thermistor TH22 Linear expansion valve Gas pipe Liquid pipe Flare connection Gas pipe Liquid pipe PKFY P24NKMU E2 PKFY P30NKMU E2 15 88 5 8 9 52 3 8 Item Model Unit mm inch Gas pipe thermistor 2 TH24 15 88 5 8 9 52 3 8 PKFY P24NKMU E2 TH PKFY P30NKMU E2 TH OCH518 ...

Страница 9: ...mp TH22 is 32 F or less in 16 minutes from compressors start up anti freezing control starts and the thermo OFF Released condition The timer which prevents reactivating is set for 3 minutes and anti freezing control is cancelled when any one of the following conditions is satisfied Liquid pipe temp TH22 turns 50 F or above The condition of the thermo OFF has become complete by thermostat etc The o...

Страница 10: ... Over 64 F ON OFF T1 83 F 83 F T1 79 F 79 F T1 75 F 75 F T1 Unconditional 9 3 7 3 5 3 3 3 10 3 Dry thermo OFF 2 Fan Note Remote controller setting is not acceptable Dry thermo Fan speed notch Excluding the following Room temp 64 F ON OFF Low Low Stop 3 Vane up down vane change Same control as COOL operation PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON ...

Страница 11: ...ction on the vane s downward blow setting Same control as COOL operation PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF û Fû C û Fû C ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ON OFF Hr AFTER FILTER FUNCTION ONLY1Hr WEEKLY SIMPLE AUTO OFF 6 3 FAN OPERATION How to operate Press POWER ON OFF button Press the operation MODE button to displ...

Страница 12: ...the auxiliary heater ON to OFF thermostat or operation stop etc the indoor fan operates in Low mode for 1 minute This control is same for the model without auxiliary heater 1 STAND BY will be displayed during the hot adjust mode To be continued on the next page By the remote controller setting switch of 2 speeds Type Fan speed notch Low High 2 speeds PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR T...

Страница 13: ...ails HEAT mode for room temperature Desired temperature COOL mode for room temperature Desired temperature 1 HEAT mode ĺ COOL mode Room temperature Desired temperature 3 F or 3 min has passed 2 COOL mode ĺ HEAT mode Room temperature Desired temperature 3 F or 3 min has passed 1 Initial value of operation mode Remarks 2 Mode change Same control as cool operation 3 COOL mode Same control as heat ope...

Страница 14: ... LEV White Yellow Orange Blue Red Brown CN60 Refer to 7 1 3 7 1 2 Liner expansion valve 7 1 1 Thermistor 4 ĭ4 3 6 5 ĭ3 2 ĭ2 1 ĭ1 ĭ4 ĭ3 ĭ2 ĭ1 Controller board Drive circuit Connector CN60 DC12V Brown Red Blue Orange Yellow White M 4 6 2 3 5 1 Blue Brown Yellow Orange Red White Linear expansion valve Thermistor characteristic graph Room temperature thermistor TH21 Liquid pipe temperature thermistor ...

Страница 15: ...or of lead wire and missing terminal of the con nector Exchange the linear expan sion valve Exchange the linear expan sion valve If large amount of refriger ant is leaked exchange the linear expansion valve Disconnect the connector at the controller board then check the continuity Measure the resistance between each coil white red yellow brown orange red blue brown using a tester It is normal if t...

Страница 16: ...d 3 of the fan connector VDC DC294 325V TEST POINT VCC between 4 and 3 of the fan connector VCC DC15V Wiring recovery Replace indoor controller board Replace indoor controller board Replace the fan motor Replace the fan motor Indoor controller board fuse check Replace indoor controller board Replace the fan motor Is the voltage normal Is there contact failure No Yes No No Is the fuse normal Replac...

Страница 17: ...subcool 2 ON OFF 1 2 3 4 5 6 7 8 ON OFF 1 2 3 4 5 6 7 8 9 10 Address board Initial setting Initial setting SW3 Function selection SW2 Capacity code Before power supply ON switch SW1 Mode Effective timing Under suspension selection Switch Pole Function Operation by switch Remarks Built in remote controller Indoor unit Changing the opening of linear expansion valve during thermo OFF 1 SW1 7 OFF ON O...

Страница 18: ...ress the SET button using a pointed implement Check that the remote controller s display has stopped before continuing MODEL SELECT flashes and the model No 3 digits appears steadily lit 2 Press the MINUTE button twice The pair number appears flashing 3 Press the temperature buttons to select the pair number to set 4 Press the SET button using a pointed implement The set pair number is displayed s...

Страница 19: ... to the terminal block TB5 M NET transmission connecting wire 24 30VDC non polar Power supply from outdoor unit SW3 Function setting CN2G Pipe temperature thermistor Gas2 TH24 CN24 External heater 12VDC 1 CN60 Linear expansion valve LEV output 12VDC pulse output CNRU Connect to the wireless remote controller board W B CN151 Vane motor output 12VDC pulse FUSE 3 15A 250V CNMF Connect to the fan moto...

Страница 20: ...0 7 3 3 Address board PKFY P24NKMU E2 TH PKFY P30NKMU E2 TH SW1 Function setting SW12 Address setting 10ths DIGIT SW11 Address setting 1s DIGIT 7 3 2 Wireless remote controller board PKFY P24NKMU E2 TH PKFY P30NKMU E2 TH SW14 Branch No CN301 Connect to the indoor controller board I B OCH518 ...

Страница 21: ...e screw and hook of address board case See Photo 2 3 Disconnect the connectors of address board 4 Remove the front and side electrical box covers each 1 screw 5 Disconnect the connectors on the indoor controller board See Photo 3 6 Remove the switch board holder and open the cover 7 Pull out the indoor controller board toward you then remove the indoor controller board and switch board See Photo 3...

Страница 22: ...EMBLY with VANE and VANE MOTOR AND DRAIN HOSE 1 Remove the panel and corner box Refer to procedure 1 2 Remove the electrical box covers Refer to procedure 2 3 Disconnect the vane motor connector CN151 on the indoor controller board 4 Pull out the drain hose from the nozzle assembly and remove nozzle assembly See Photo 5 Photo 4 Connect for ground Photo 5 Photo 6 Fixture Electrical box 5 REMOVING T...

Страница 23: ... 3 screws fixing the left side of the heat exchanger See Photo 9 10 Lift the heat exchanger and pull out the line flow fan to the lower left Photo 7 7 REMOVING THE LIQUID PIPE THERMISTOR AND GAS PIPE THERMISTOR 1 Remove the panel and the corner box Refer to procedure 1 2 Remove the electrical box covers Refer to procedure 2 3 Remove the water cut See Photo 2 4 Remove the liquid pipe thermistor and...

Страница 24: ...ure 4 3 Remove the water cut 4 Remove the pipe thermistors Refer to procedure 7 5 Disconnect the connector CN60 on the indoor controller board and the connector for ground wire 6 Remove 3 screws fixing the left side of the heat exchanger See Photo 9 7 Remove the heat exchanger with LEV 9 REMOVING THE ROOM TEMPERATURE THERMISTOR 1 Remove the panel and corner box Refer to procedure 1 2 Remove the el...

Отзывы: