Mitsubishi Electric CITY MULTI PFD-500VM-A Скачать руководство пользователя страница 9

9

GB

D

F

I

NL

E

P

GR

RU

TR

3.

Do not provide any odor trap at the drain discharge port.

4. Put the end of the drain piping in a position where no odor is generated.

5. Do not put the end of the drain piping in any drain where ionic gases are

generated.

6. Check drainage by pouring water into the drain pan and check to see that it

drains properly.

7. Check for ease of operation of the fault detection float switch in the drain pan,

and breakage of leads.

8. Provide a drain trap to the drain piping installed on site.

* The loop on the drain hose provided with the unit does not function as a trap;

it is only used to drain water to the main drain pan at the bottom of the prod-
uct.

7.1. Power supply wiring

7. Electrical wiring

Precautions on electrical wiring

 Warning:

Electrical work should be done by qualified electrical engineers in accord-
ance with “Engineering Standards For Electrical Installation” and supplied
installation manuals. Special circuits should also be used. If the power cir-
cuit lacks capacity or has an installation failure, it may cause a risk of elec-
tric shock or fire.

1. Be sure to take power from the special branch circuit.

2. Be sure to install an earth leakage breaker to the power.

3. Install the unit to prevent that any of the control circuit cables (remote control-

ler, transmission cables) is brought in direct contact with the power cable out-
side the unit.

4. Ensure that there is no slack on all wire connections.

5. Some cables (power, remote controller, transmission cables) above the ceiling

may be bitten by mouses. Use as many metal pipes as possible to insert the
cables into them for protection.

6. Never connect the power cable to leads for the transmission cables. Otherwise

the cables would be broken.

7. Be sure to connect control cables to the indoor unit, remote controller, and the

outdoor unit.

8. Put the unit to the ground on the outdoor unit side.

9. Select control cables from the conditions given in below.

 Caution:

Be sure to put the unit to the ground on the outdoor unit side. Do not con-
nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone
earth cable. Incomplete grounding may cause a risk of electric shock.

Types of control cables

1. Wiring transmission cables

Types of transmission cables

Shielding wire (2-core)

CVVS or CPEVS <max length: 200 m>.

Cable diameter

More than 1.25 mm

2

2. Remote controller cables

Types of cables

Cable diameter

Length

MA remote controller

2-core cable (unshielded)

0.3 to 1.25 mm

2

Less than 200 m

Note:
1. Bear in mind ambient conditions (ambient temperature,direct sunlight,

rain water,etc.) when proceeding with the wiring and connections.

2. The wire size is the minimum value for metal conduit wiring. The power

cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.

Model
Power supply
Power supply wiring cross-section
Earth wiring cross-section
Earth leakage
breaker
Wiring breaker (NFB)

PFD-P250VM-A

2.5 mm

2

2.5 mm

2

20 A

20 A

Type <capacity>
Rated sensitivity

Note:
If the rise portion is long, there will be a lot of returned water in an operation
stop, generating slime or odor during off-season. Ensure that the rise por-
tion is at a minimum.

 Caution:

Always prepare the water seal by filling the trap with water from the drain
pan during test operation. Inject water into the drain trap during the periodic
check (six-monthly) to check water-sealing. If the trap is not filled with water,
it will cease to function and this may result in leaks.

 Caution:

Pipe the drain piping to ensure that it discharges drain, and insulate it to
prevent dew condensation. A failure to the piping work may cause water
leakage and so wet your property.

3. Specific wiring requirements should adhere to the wiring regulations of

the region.

4. Wiring cross-sections noted are the minimum values for metal and plas-

tic wiring conduits (containing up to three cables).

Power supply cords of appliances shall not be lighter than design 245 IEC 53
or 227 IEC 53.

A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.

 Caution:

1. Use only breakers and fuses of the correct capacity. Use of larger capac-

ity fuses, or wire may result in a fault and smoke or flames.

2. Wire the power supply so that no tension is imparted. Otherwise discon-

nection, heating or fire result.

7.2. Connecting remote controller, indoor

and outdoor transmission cables

Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)

The “S” on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.

Do not connect the indoor unit terminal block (TB5) to another indoor unit ter-
minal block (TB5) that is connected to a different outdoor unit.

If it is a Model 500, always ensure the connection between each outdoor unit
passes across the “A” and “B” pins (TB7) of the central controller’s transmis-
sion cable terminal block. (See Fig. 7.4.2.)

The shielded grounding wire for the central controller's transmission cable must
pass across the S pin of the central controller's transmission cable terminal
block (TB7) of each outdoor unit.

When a feeding device is not connected to the central controller’s transmission
cable, replace the feed switching connecter of a single outdoor unit (CN41)
with CN40. In this case, the shielded grounding wire for the central controller's
transmission cable connects the S terminal block of the terminal block of a
single outdoor unit (TB7) that had its connector replaced to CN40, to the ground-
ing screw 

.

When a feeding device is connected to the central controller’s transmission
cable, the shielded grounding wire of the central controller's transmission ca-
ble must be grounded with the 

 pin of the feeding device. In this case, the

feed switching connector (CN41) of the outdoor unit is not replaced.

Install a remote controller following the manual supplied with the remote con-
troller.

Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)

[Fig. 7.2.1]

 

(P.3) MA Remote controller

<A> Model 250

<B> Model 500

A

Terminal block for indoor transmission cable

B

Terminal block for outdoor transmission cable

C

MA Remote controller

DC 9 to 13 V between 1 and 2 (MA remote controller)

[Fig. 7.2.2]

 

(P.3) MA Remote controller

<A> Model 250

<B> Model 500

A

Non-polarized

B

Upper level

C

Lower level

D

MA Remote Controller

Note:
1. Ensure that the wiring is not pinched when fitting the terminal box cover.

Pinching the wiring may cut it.

2. Put the transmission cable earth via the outdoor unit’s earth terminal 

to the ground.

PFD-P500VM-A

4.0 mm

2

4.0 mm

2

30 A

30 A

30 mA less than 0.1 s

380 - 415V

Содержание CITY MULTI PFD-500VM-A

Страница 1: ...d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze install...

Страница 2: ...ing material procured on site G Site thermal insulating material F Bind with band or tape 235 210 260 340 420 205 210 50 395 110 15 15 1160 70 1050 70 1895 800 5 5 1200 1A K Refrigerant piping flange gas O Air outlet M Drain piping joint outlet Rp1 N As seen from bottom face A L Refrigerant piping flare ø12 7 liquid J Location of refrigerant piping A Gas B Liquid E Unit weight PFD P250VM A 350 kg ...

Страница 3: ...door transmission cable C MA Remote controller DC10 13V A B 1 2 A2 1 2 A Non polarized D MA Remote Controller Upper level TB5 1 C Lower level TB15 B2 S S A1 B1 TB5 2 DC10 13V A B 1 2 A1 1 2 A Non polarized D MA Remote Controller Upper level TB5 C Lower level TB15 B1 S B B Fig 7 2 2 7 3 Fig 7 3 1 NO 2 NO 1 local nomal CN2M CN29 CN21 CN20 CN3A CN31 CN25 CN60 CN81 CN42 CN24 CN70 CNT CND CN3T CN23 CNV...

Страница 4: ...1 2 M2 A1 B2 S 52 OC PUD P250YMF C 02 TB15 MA 1 2 A1 B2 TB3 TB7 M1 M2 M1 M2 S M1 TB5 TB5 1 TB5 2 M2 S 51 OC IC model 250 IC model 500 01 TB3 TB7 M1 M2 M1 M2 S M1 TB15 MA 1 2 M2 A1 B2 S 53 OC 03 04 M1 M2 S TB3 TB7 M1 M2 M1 M2 S 54 OC OC A B S A B S TB2 2 The Model 250 indoor unit contains one indoor controller board A CN41 as it is A Replace CN41 with CN40 B Group 1 C Group 2 A CN41 as it is B CN41...

Страница 5: ... wiring G Low voltage system wiring E model 500 only E model 500 only Fig 7 5 2 External power supply SW12 Pulse input of start or stop DC12 24 V Input current per contact Approximately 10 mA DC12 V Remote Start Stop switch Toggles ON OFF each time switch is pressed pulse input SW11 Remote Start Stop switch Toggles ON OFF each time switch is pressed pulse input Micro current contacts DC12 V 1 mA D...

Страница 6: ...in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstall...

Страница 7: ...erio rate 1 3 Before getting installed Caution Do not install the unit where combustible gas may leak If the gas leaks and accumulates around the unit an explosion may result Do not use the air conditioner where food pets plants or artwork are kept The quality of the food etc may deteriorate Do not use the air conditioner in special environments Oil steam sulfuric smoke etc can significantly reduc...

Страница 8: ...not provide any trap or irregularity on the way 2 Ensure that any cross wise drain piping is less than 20 m excluding the differ ence of elevation If the drain piping is long provide metal braces to prevent it from waving Never provide any air vent pipe Otherwise drain may be ejected 4 Installing the unit 4 2 Fixing unit Always ensure that the indoor unit is installed horizontally If it is install...

Страница 9: ...r seal by filling the trap with water from the drain pan during test operation Inject water into the drain trap during the periodic check six monthly to check water sealing If the trap is not filled with water it will cease to function and this may result in leaks Caution Pipe the drain piping to ensure that it discharges drain and insulate it to prevent dew condensation A failure to the piping wo...

Страница 10: ...n of indoor unit addresses varies with the system at site Set them referring to technical data If connecting a controller inside a central controller the address of the two controllers inside the Model 500 indoor unit must always be set in the same group Fig 7 4 1 P 4 When there is a single Model 250 unit A CN41 as it is 1 The numbers shown in the square are addresses 2 The Model 250 indoor unit c...

Страница 11: ...supplied to MA remo con after finishing the initial mode correctly HO is flashing during the initial mode Max 20sec The units cannot operate if transmission line is incorrect Wiring Method 1 Check the indoor unit settings Refer to 7 Electrical Wiring Diagram 2 When using the external output function connect the signal lines to the exter nal output terminal TB22 of the unit as appropriate for the a...

Страница 12: ...ler Test run complete 4 Set indoor unit Normal Local switch of indoor unit to Normal Check that the Normal Local switch is set to Normal after test run Notes 1 An error code will be appeared on the remote controller if the Fault lamp on the indoor unit is lit during test run Refer to the Outdoor Units Installation Manual for details of error codes 2 Set DIP SW3 7 to ON if operation cannot be conti...

Страница 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...