VIII
Troubleshooting ]
- 25 -
HWE08010
GB
4. Voltage test points on the control board
1. PEFY-P06,08,12,15,18,24NMSU-E
Fuse
Fuse(AC 250V 6.3A)
CND
Power supply voltage (208 -
230VAC)
CN2M
For M-NET transmission cable
connection (24 - 30VDC)
SWE
Emergency operation
SW2
Capacity setting
SW4
Function setting
CN42
For address board connection
SW3
Function setting
CN81
For address board connection
CN32
Remote start/stop adapter
CN3A
For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3.))
CN4Y
For fan control
CN52
Remote display
CN51
Centralized control
CN41
JAMA standard HA terminal A
CN44
Thermistor (liquid/gas tempera-
ture)
CN4F
Float thermistor
CN24
For heater control
CN20
Thermistor (Inlet temperature)
CN3C
Indoor-outdoor transmission
(0 - 24VDC)
CNMF
Fan motor output
1 - 4: 310 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CNP
Drain-up mechanism output
(200VAC)
(*1)
V
FG
Voltage on the (-) side of PC941
and C25
(Same with the voltage between 7
(+) and 4 (-) of CNMF)
V
CC
Voltage between the C25 pins
15 VDC
(Same with the voltage between 5
(+) and 4 (-) of CNMF)
Vsp Voltage between the C951 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in opera-
tion)
(Same with the voltage between 6
(+) and 4 (-) of CNMF)
Fuse
CND
С25(*1)
CN2M
SWE
SW2
SW4
CN42
SW3
CN81
CN32
LED2 CN3A
CN60 CN4Y
CN52
CN51
CN41
CN44
CN4F
CN20
CN24
CN3C
LED1
PC941(*1)
C951(*1)
CNMF
CNP