(1) On the ducted model units (except the Fresh air intake type), turning on the heater with the fan setting set to OFF requires that
the DIP S/W and connectors on the indoor units*1 are set on site. (in case of PEFY-P06,08,12,15,18,24NMSU-E)
*1: DIP SW 3-4, CN24, and CN4Y
(2) On the Fresh air intake type units, the heater cannot be turned on with the fan setting set to OFF.
(3) Non-ducted models do not require the settings described in Section (1) above.
(4) Back-up heating will not be performed when the heater turns on while demand control is performed (not a request item).
(5) This is applicable only to the R410 series. Make the settings for the following dip switches on the outdoor unit control board
before switching on the power.
2. Fan
control
By using the optional parts PAC-YU25HT, fan speed can be controlled.
*depend on SW1-7/1-8
Table.2
Heater control #A
Heater OFF
Inlet air temp.
set temp.
Heater ON
Inlet air temp. < set temp.-4°F
Heater control #B
Heater OFF
Inlet air temp.
set temp.
Heater ON
Inlet air temp. < set temp.-1.8°F
<For heater>
The value "4°F" is modifiable from 1.8°F to 9°F by maintenance tool.
Pattern
Duct unit PE/PD/PF-NR(NL)
Î
(PEFY-P06,08,12,15,18,24NMSU-E)
CN4Y for FAN control (YU25)
DIP S/W3-4 (Indoor unit)
Fan in defrost
1
Disabled
OFF
Stop (Heater OFF)
2
ON
L / LL / Set * (Heater ON)
3
Enabled
OFF
Stop (Heater OFF)
4
ON
Stop (Heater ON)
SW3-1
SW1-7
SW1-8
Fan speed *1
OFF
OFF
OFF
Very low
OFF
ON
OFF
Low
OFF
OFF
ON
Remote controller setting
OFF
ON
ON
Stop
(Remote controller setting *2)
ON
ON
ON
Stop
(Remote controller setting *2)
*1 The fan operates at the same speed settings as shown in this table
during the Heating Thermo-OFF mode.
*2 If Pattern 2 in the table above is selected for the fan control pattern,
the fan will follow the setting of the remote controller.
Set temp.
Set temp.-1.8°F
Set temp.-4°F
Inlet air temp.
Heater output
OFF
ON
Set temp.
Set temp.-1.8°F
Inlet air temp.
Heater output
OFF
ON