[
VII
Microprocessor Control ]
- 14 -
HWE08010
GB
This control is same for the model without auxiliary heater.
(4) Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in [Extra low].
(5) Heat defrosting mode
The indoor fan stops.
3. Drain
pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
5. Auto operation [Automatic cool / heat change over operation]
1. Initial value of operation mode
(1) HEAT mode for room temperature < Desired temperature
(2) COOL mode for room temperature
Desired temperature
2. Mode
change
(1) HEAT mode -> COOL mode
Room temperature
Desired tempe 3°F. or 3 min. has passed
(2) COOL mode -> HEAT mode
Room temperature
Desired temperature - 3°F. or 3 min. has passed
3. COOL
mode
(1) Same control as cool operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display AUTO.
3. Press the [Set Temperature] button to set the desired tempera-
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Automatic 67 to 83°F
ON
OFF
15sec.
15sec.
15sec.
1min.30sec.
1min.30sec.
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Содержание City Multi PEFY-P06NMSU-E
Страница 5: ...iv HWE08010 GB ...
Страница 7: ...HWE08010 GB ...