9.1. Power supply wiring

[Indoor unit]

Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.

A switch with at least 3 mm [1/8 in.] contact separation in each pole shall be
provided by the Air conditioner installation.

Power cable size: more than 1.5 mm

2

 [AWG16]

[Fig. 9.1.1] (P.5)

A

Switch 16 A

B

Overcurrent protection 16 A

C

Indoor unit

D

Total operating current be less than 16 A

E

Pull box

2. Remote controller cables

Types of cables

Cable diameter

Length

MA remote controller

Sheathed 2-core cable (unshielded) CVV

0.3 to 1.25 mm

2

  [AWG22 to 16]

Less than 200 m

M-NET remote controller

Sheathed 2-core cable (unshielded) CVV

0.3 to 1.25 mm

2

  [AWG22 to 16]

Add any portion in excess of 10 m [32 ft] to within the longest allowable transmis-
sion cable length 200 m [656 ft] (Shielding portion is more than 1.25 mm

[AWG16])

<Table 1>

System configuration

For a single-refrigerant system

For a multi-refrigerant system

Transmission cable length

Less than 120 m [394 ft]

More than 120 m  [394 ft]

Regardless of length

Facility example

(for electrical noise judgment)

Types of transmission

cables

Residence or independent store

without electrical noise

VCTF, VCTFK, CVV, CVS, VVR,

VVF, VCT or shielding wire

CVVS or CPEVS

Building, clinic, hospital or communications

station without electrical noise supposedly

generated from inverter equipment, private

power generator, high-frequency medical

equipment, radio-used communications

equipment and so on

All facilities

Shielding wire CVVS or CPEVS

Length

Less than 120 m [394 ft]

Less than 200 m [656 ft]

 

[656 ft]

9. Electrical wiring

Precautions on electrical wiring

 Warning:

Electrical work should be done by qualified contractors in accordance with
“Engineering Standards For Electrical Installation” and supplied installation
manuals. Special circuits should also be used. If the power circuit lacks ca-
pacity or has an installation failure, it may cause a risk of electric shock or
fire.

1. Be sure to install a ground breaker to the power.

2. Install the unit to prevent that any of the control circuit cables (remote control-

ler, transmission cables) coming in direct contact with the power cable outside
the unit.

3. Ensure that there is no slack on all wire connections.

4. Some cables (power, remote controller, transmission cables) above the ceiling

may be bitten by rodent. Use as many metal pipes as possible to protect the
cables.

5. Never connect the power cable to leads for the transmission cables. Otherwise

the cables would be broken.

6. Be sure to connect control cables to the indoor unit, remote controller, and the

outdoor unit.

7. Put the unit to the ground on the outdoor unit side.

8. Select control cables from the conditions given in page 

12

.

 Caution:

Be sure to put the unit to the ground on the outdoor unit side. Do not con-
nect the ground cable to any gas pipe, water pipe, lightening rod, or telephone
ground cable. Incomplete grounding may cause a risk of electric shock.

Types of control cables

1. Wiring transmission cables

Types of transmission cables

Design wiring in accordance with the following table <Table 1>.

Cable diameter

More than 1.25 mm

[AWG16]

[Selecting non-fuse breaker (NF) or ground breaker (NV)]

To select NF or NV instead of a combination of Class B fuse with switch, use the
following:

In the case of Class B fuse rated 15 A or 20 A,

NF model name (MITSUBISHI): NF30-CS (15 A) (20 A)
NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)

Use an ground breaker with a sensitivity of less than 30 mA 0.1 s.

[Outdoor unit]
Thickness of wire for main power supply, on/off capacities

<Power source: 460V>

Main cable

Swtich (A)

Minimum wire thickness (mm

2

 [AWG])

Branch

Capacity

Fuse

Breaker for

Ground

Model

Unit combination

Breaker for current leakage

wiring (NFB)(A)

Outdoor

unit

PUHY-P72YHMU-A(-BS)

-

PUHY-P96YHMU-A(-BS)

-

PUHY-P120YHMU-A(-BS)

-

15 A 30 mA or 100 mA 0.1 sec. or less
20 A 30 mA or 100 mA 0.1 sec. or less
25 A 30 mA or 100 mA 0.1 sec. or less

Maximum

current (A)

10.3
16.4
22.6

2.1 [14]

-

2.1 [14]

15

15

15

3.3 [12]

-

3.3 [12]

20

20

20

5.3 [10]

-

5.3 [10]

25

25

25

<Power source: 208V / 230V>

Main cable

Swtich (A)

Minimum wire thickness (mm

2

 [AWG])

Branch

Capacity

Fuse

Breaker for

Ground

Model

Unit combination

Breaker for current leakage

wiring (NFB)(A)

Outdoor

unit

PUHY-P72THMU-A(-BS)

-

PUHY-P96THMU-A(-BS)

-

PUHY-P120THMU-A(-BS)

-

30 A 30 mA or 100 mA 0.1 sec. or less
40 A 30 mA or 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less

Maximum

current (A)

22.7
36.3
49.9

5.3 [10]

-

5.3 [10]

30

30

30

13.3 [6]

-

13.3 [6]

40

40

40

21.2 [4]

-

21.2 [4]

50

50

50

Содержание City Multi PEFY-AF1200CFM

Страница 1: ... correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte English Français ...

Страница 2: ...8 B Liquid refrigerant piping brazing connection of main coil ø9 52 3 8 C Gas refrigerant piping brazing connection of reheat coil ø22 2 7 8 D Liquid refrigerant piping brazing connection of reheat coil ø9 52 3 8 E Drain pipe O D ø32 1 1 4 primary draining F Drain pipe O D ø32 1 1 4 secondary draining G Drain pipe O D ø32 1 1 4 6 6 2 Fig 6 2 1 Unit mm in 395 15 9 16 96 3 13 16 604 23 13 16 524 20 ...

Страница 3: ... AF1200CFMR C B D A E E F E F Insulation pipe small accessory G Caution Pull out the insulation on the refrigerant piping at the site braze the piping and replace the insulation in its original position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant pi...

Страница 4: ...tion must be positioned up Fig 7 2 3 A Indoor unit B Insulation short accessory C Tie short accessory D Attaching the band E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC field supplied H Insulation field supplied I Max 145 5 mm 5 23 32 7 32 in D E H G I F B C 5 7 32 A 25 1 Unit mm in Unit mm in SWE Correct piping Wrong piping A Insulation 9 mm 3 8 in or more B Decli...

Страница 5: ... A Non polarized B TB15 C Remote Controller D TB5 Fig 9 2 3 Fig 9 2 4 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L1 L2 G C D A S M2 M1 B 1 2 L1 L2 G DC24 30V A B 1 2 C E D C B A F E 9 2 Fig 9 1 2 PEFY AF1200CFM Fig 9 1 3 PEFY AF1200CFMR B A B A C T S HMU 3 208 230V Y S HMU 3 460V L1 L2 L3 208 230V L1 L2 Ground Ground D A Switch Breakers for wiring and current leak B Breakers for current leak C Outdoor uni...

Страница 6: ...Shield wire D The ground wire from two cables are connected together to the S terminal Dead end connection E Insulation tape To keep the ground wire of the shielded cable from coming in contact with the transmission terminal Indoor controller board 9 3 Fig 9 3 3 Fig 9 3 4 Fig 9 5 1 Fig 9 3 5 9 5 A Terminal block box B Knockout hole C Remove A Screw 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B C A B A A B ...

Страница 7: ... properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditio...

Страница 8: ...ng rods or telephone ground lines Improper grounding may result in electric shock Install the power cable so that tension is not applied to the cable Tension may cause the cable to break and generate heat and cause a fire Install a leak circuit breaker as required If a leak circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and ...

Страница 9: ...leaks Be sure to check the position s s s s s Use a level to check that the surface indicated by A A A A A is at level Ensure that the hanging bolt nuts are tightened to fix the hanging bolts s s s s s To ensure that drain is discharged be sure to hang the unit at level using a level Caution Install the unit in horizontal position If the side with the drain port is in stalled higher it may cause w...

Страница 10: ...iginal position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant piping M Ensure that there are no gaps between the insulation and the body N Tie long accessory O Ensure that there is no gap here Joint should face up For PEFY AF1200CFMR Use the supplied ...

Страница 11: ...unit pipe This metal brace should be 50 cm 19 11 16 in away from the indoor unit s flare connection Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant specified on the unit Mixing of a different refrigerant air etc may cause the refrigerant cycle to mal function and result in severe damage Caution Use refrigerant piping made of C1220 Cu DHP pho...

Страница 12: ...g in direct contact with the power cable outside the unit 3 Ensure that there is no slack on all wire connections 4 Some cables power remote controller transmission cables above the ceiling may be bitten by rodent Use as many metal pipes as possible to protect the cables 5 Never connect the power cable to leads for the transmission cables Otherwise the cables would be broken 6 Be sure to connect c...

Страница 13: ...n polarized 2 wire Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire Connect the remote controller s transmission cable within 10 m 32 ft using a 0 75 mm2 AWG18 core cable If the distance is more than 10 m 32 ft use a 1 25 mm2 AWG16 junction cable Fig 9 2 1 P 5 MA Remote controller Fig 9 2 2 P 5 M NET Remote controller A Terminal block for indoor transmissi...

Страница 14: ...ntrol board reheat unit that equals the address of the right control board main unit plus 1 Fig 9 5 2 P 6 A Indoor controller board main B Indoor controller board reheat The rotary switches are all set to 0 when shipped from the factory These switches can be used to set unit addresses and branch numbers at will The determination of indoor unit addresses varies with the system at site Set them refe...

Страница 15: ... un incendie ou de la fumée pourrait en résulter Mettez fermement en place le couvercle des bornes de l appareil extérieur panneau Si le couvercle des bornes panneau n est pas mis en place correctement il se peut que de la poussière ou de l eau s infiltre dans l appareil extérieur et par conséquent il y aura un risque d incendie ou d électrocution Lors du déplacement et de l installation du climat...

Страница 16: ...ut que le climatiseur ait un effet nuisible sur ce genre d équipements en faisant du bruit qui gênerait les traitements médicaux ou l envoi d images N installez pas l appareil sur une structure qui pourrait causer des fui tes Lorsque l humidité de la pièce dépasse 80 ou lorsque le tuyau d écoule ment est bouché il se peut que des gouttes d eau tombent de l appareil intérieur Veillez à fournir une ...

Страница 17: ... une distribution homogène de l air dans la pièce Ne pas installer l appareil dans un endroit sujet à des éclaboussures de graisse ou à de grandes quantités de vapeur Ne pas installer l appareil dans un endroit avec arrivée de gaz combustible entrepôt de gaz ou sujet à des fuites de gaz Ne pas installer l appareil dans un endroit contenant des équipements qui pro duisent des ondes de haute fréquen...

Страница 18: ...portez vous au manuel de l appareil extérieur Brasez les connexions des tuyaux Précaution Installer les tuyaux de réfrigérant pour l appareil intérieur conformément aux instructions suivantes 7 Raccordement des tuyaux de réfrigérant et d écoulement 7 1 Mise en place des tuyaux de réfrigérant Les travaux de raccordement des tuyaux doivent être faits conformément aux ins tructions des manuels d inst...

Страница 19: ...sières saletés de particules de rasage d huile d hu midité ou de n importe quel autre contaminant dangereux N utilisez jamais les tuyaux de réfrigérant déjà en place La quantité importante de chlore contenue dans les réfrigérants tradition nels et l huile réfrigérante des tuyaux actuels provoquera la détérioration du nouveau réfrigérant Entreposez à l intérieur la tuyauterie à utiliser et gardez s...

Страница 20: ...se en place des câbles de transmission Types de câbles de transmission Concevoir le câblage conformément aux indications reprises dans le tableau suivant Table1 Diamètre des câbles Plus de 1 25 mm2 AWG16 8 Raccords des conduites Lors du raccordement des conduits insérer une protection en canevas entre le corps principal et le tuyau Utiliser des composants pour conduits ininflammables Installer une...

Страница 21: ...urce d alimentation 208V 230V Câble principal Commutateur A Épaisseur minimale du câble mm2 AWG Embranchement Capacité Fusible Disjoncteur pour Terre Modèle Combinaison d appareil Disjoncteur pour fuite de courant câblage NFB A Appareil extérieur PUHY P72THMU A BS PUHY P96THMU A BS PUHY P120THMU A BS 30 A 30 mA ou 100 mA 0 1 sec ou moins 40 A 30 mA ou 100 mA 0 1 sec ou moins 50 A 100 mA 0 1 sec ou...

Страница 22: ...borne de transmission 5 Lorsque le câblage est terminé vérifier qu il n y a pas de jeu dans les con nexions et fixer le couvercle au bloc de raccordement en procédant dans l or dre inverse au démontage Remarques Faire attention à ne pas coincer les câbles ou les fils en rattachant le couvercle de la boîte de commandes sinon ceux ci risquent de se dé brancher Lors de la fixation de la boîte de comm...

Страница 23: ...GB E F I NL E P GR RU TR ...

Страница 24: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: