27
GB
11. Confirmation of proper operation
Checking the panel heater for normal operation
(1) Use a tester to check that the heater wire is not broken for proper operation.
(2) Check the output voltage for proper circuit operation.
• Energizing conditions*1: Heating mode, outside temperature of 4°C or below, and the compressor is in operation
*1 To meet the above conditions, cool the outdoor temperature sensor (TH7) using a cold spray. When cooling the sensor, make
sure to close the control box panel to keep the cold spray from getting on the board inside of the control box.
• Use the supplied terminal block for the panel heater.
• Switch setting is required to use the panel heater.
12. The following symptoms do not indicate malfunctions.
Situation
Explanation
The heater is not energized at TH7 ≤ 4°C.
• Panel heater ON conditions are not met.
- Panel heater ON conditions: Outdoor temperature is 4°C or
below (TH7 ≤ 4°C), and heating operation (including defrost
operation) is being performed.
To prevent burn injury, temperature of each surface is
individually controlled so that the energization is stopped for
areas where the heater sheet metal temperature becomes too
high. Therefore not all heaters may be energized.
* Note: Resistance at the terminal that stops the panel heater is
1440 Ω ± 7% when the unit is turned off and the panel heater
surface temperature is 40°C or below. (If the resistance is
2880 Ω ± 7%, either of the cables may be broken.)
The panel heater is cold even though the heater ON
conditions are met.
The outdoor unit performs operation by sucking in outside air.
Therefore the panel heater tends to be cold while the outdoor
unit is in operation. Check the panel heater during defrost.
* Note: The panel heater temperature during the defrost
operation ≈ outdoor tempe 15 deg
The heater does not turn off when TH7 ≥ 4°C.
• Panel heater OFF conditions are not met.
- Panel heater OFF conditions: The outdoor unit is in cooling
mode or stop mode, or the compressor is stopped, or
[outdoor temperature is above 7°C (TH7 > 7°C) and three
minutes have passed since the defrost operation is
completed].
The drain water is drained from the top of the outer panel of
the outdoor unit.
Even when the panel heater is turned on, it is normal that
water is drained from the outer panel of the outdoor unit.
Ice between the outer panel and the inner panel does not melt.
Water is drained from the outer panel of outdoor unit because
the panel heater is used for maintaining water drainage from
the outdoor unit panel.
Ice is formed at both edges of the heater.
The center part of the heater is heated to collect and drain
water. Therefore ice may be formed at both edges.
Water freezes between units that are densely installed.
If units are installed too close to each other, drain water from
the heater may freeze and accumulate between units. There
will not be a problem unless the top panel of the heater is
covered with ice.