1. Electrical work
DATA U5
SYSTEM DESIGN
Syste
m H
1-3. Power cable specifications
PUHY-HP-T(S)HMU
Symbols: MCA : Min. Circuit Amps
SC
: Starting Current
RLA
5.3
6.7
5.3
5.3
6.7
6.7
15
15
15
15
15
15
0.92
0.92
0.92
0.92
0.92
0.92
Model
Outdoor Units
Volts
Hz
Unit Combination
Voltage range
Max. Fuse(A)
MCA(A)
Compressor
Output(kW)
SC(A)
Output(kW)
Fan
RLA(A)
RLA(MAX)(A)
PUHY-HP72THMU-A
PUHY-HP96THMU-A
PUHY-HP
144TSHMU-A
PUHY-HP
192TSHMU-A PUHY-HP96THMU-A
PUHY-HP96THMU-A
PUHY-HP72THMU-A
PUHY-HP72THMU-A
208 / 230V
208 / 230V
208 / 230V
208 / 230V
208 / 230V
208 / 230V
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
188 to 253V
19.4 / 17.6
28.2 / 25.5
19.4 / 17.6
19.4 / 17.6
28.2 / 25.5
28.2 / 25.5
38.4 / 38.4
52.4 / 52.4
38.4 / 38.4
38.4 / 38.4
52.4 / 52.4
52.4 / 52.4
53
71
53
53
71
71
60
75
60
60
75
75
: Rated Load Amps
1-2-2. Electrical characteristics of Outdoor unit of cooling mode
Thickness of wire for main power supply, ON / OFF capacities
3-phase 3-wire, 208V,60Hz
60
75
15
60
75
15
60
75
15
2.1 / 14
13.3 / 6
21.2 / 4
13.3 / 6
21.2 / 4
2.1 / 14
Main cable
Switch (A)
Minimum wire thickness (mm
2
/ AWG)
Branch
Capacity
Fuse
PUHY-HP-THMU
P72
P96
2.1 / 14
Breaker for
wiring (NFB)
Ground
60 A 100 mA 0.1 sec. or less
75 A 100 mA 0.1 sec. or less
20 A 30 mA 0.1 sec. or less
Breaker for current leakage
Indoor unit
Be sure to use specified wires to connect so that no external force is impar ted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated over current may include some amount of direct current.
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum v alue f or metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage dr ops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1 / 8 in] contact separation in each pole shall be provided by the Air conditioner installation.
CAUTION