4. Outdoor Installation
DATA U5
SYSTEM DESIGN
Syste
m H
4-3-5. Refrigerant pipe routing
4-3-4. Installation
Unit : mm[in]
Installation base perpendicular to the unit’s front panel
Installation base parallel to the unit’s front panel
221
150
251
186
(5-29/32)
83 (3-9/32)
2X2-14(9/16)X20(13/16) Oval hole
(9-29/32)
(8-23/32)
(7-11/32)
(5-23/32)
(5-3/16)
131
145
(3-13/32)
86
(23/32)
18
A
(28-13/32~28-5/8)
(28-17/32)
(760)(29-15/16)
(3-5/8)
92
724(721~727)
(Mounting pitch
)
(29-15/16)
(3-5/32)
(3-5/32)
80
760
80
(Mounting pitch)
Bottom view
(23/32)
18
Refrigerant control
valve <liquid>
Refrigerant control
valve <gas>
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in] in height.
145(5-23/32)
142(5-19/32)
PUHY-HP72THMU
PUHY-HP96THMU
Model
A
The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.
This unit allows two types of pipe routing:
• Bottom piping
• Front piping
To prevent small animals, water and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
and wires with filler plates.
CAUTION
Example of closure materials (field-supplied)
Fill the gap at the site
4 - 99