IX
Troubleshooting ]
- 143 -
HWE1113B
GB
2503
1. Error
Code
Drain sensor (Thd) fault
2. Error definition and error detection method
If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary
error, and the unit goes into the 3-minute restart delay mode.
If another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If
the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.)
This error is detected when one of the following conditions are met.
During Cool/Dry operation
Liquid pipe temperature minus inlet temperature is equal to or smaller than - 10°C [ -18°F] (except during the defrost cycle)
When the liquid temperature thermistor or suction temperature thermistor or short or open circuited.
Drain pump is in operation.
One hour has elapsed since the drain sensor went off.
Short: 90°C [194 °F] or above
Open: - 20°C [-4 °F] or below
3. Cause, check method and remedy
2503
Cause
Check method and remedy
(1)
Faulty connector (CN31) insertion.
1)
Check for connector connection failure.
Reinsert the connector, restart the operation, and check for
proper operation.
(2)
Broken or semi-broken thermistor wire
2)
Check for a broken thermistor wire.
(3)
Thermistor failure
3)
Check the resistance of the thermistor.
0°C[32 °F]:6.0k
10°C[50 °F]:3.9k
20°C[68°F]:2.6k
30°C[86°F]:1.8k
40°C[104 °F]:1.3k
(4)
Indoor unit control board (error detection circuit)
failure
4)
Replace the indoor unit control board if the problem recurs
when the unit is operated with the No.-1 and No.-2 pins on
the drain sensor connector (CN31) being short-circuited.
If the above item checks out OK, there are no problems with
the drain sensor.
Turn off the power and turn it back on.
Содержание City Multi CMB-WP108V-G
Страница 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Страница 11: ... 2 HWE1113B GB ...
Страница 27: ... I Read Before Servicing 18 HWE1113B GB ...
Страница 29: ... 20 HWE1113B GB ...
Страница 57: ... 48 HWE1113B GB ...
Страница 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Страница 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Страница 73: ... 64 HWE1113B GB ...
Страница 81: ... IV Remote Controller 72 HWE1113B GB ...
Страница 83: ... 74 HWE1113B GB ...
Страница 88: ... 79 HWE1113B GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 83 ...
Страница 89: ... 80 HWE1113B GB ...
Страница 97: ... 88 HWE1113B GB ...
Страница 127: ... 118 HWE1113B GB ...
Страница 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Страница 137: ... 128 HWE1113B GB ...
Страница 252: ... 243 HWE1113B GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 245 ...
Страница 253: ... 244 HWE1113B GB ...