I
Read Before Servicing ]
- 5 -
HWE1113B
GB
[3] Piping Materials
1. Copper pipe materials
The distinction between O-materials (Soft Annealed) and 1/2H-materials (Light Annealed) is made based on the strength of
the pipes themselves.
2. Types of copper pipes
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper.
The operation pressure of the units that use R410A is higher than that of the units that use R22.
Use pipes that have at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
For the models for use with R410A, pipes made with O-material (soft annealed) cannot be used unless they have a diameter
of at least ø19.05 (3/4") and a radial thickness of 1.2 t. Use pipes made with 1/2H-material (light annealed).
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Soft Annealed)
Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Light Annealed)
Hard copper pipes (straight pipes). They are stronger than the O-material (Soft An-
nealed) at the same radial thickness.
Maximum working pressure
Refrigerant type
3.45 MPa [500psi]
R22, R407C etc.
4.30 MPa [624psi]
R410A etc.
Pipe size (mm[in])
Radial thickness (mm)
Type
ø6.35
[1/4"]
0.8t
O-material (Soft Annealed)
ø9.52
[3/8"]
0.8t
ø12.7
[1/2"]
0.8t
ø15.88
[5/8"]
1.0t
ø19.05
[3/4"]
1.0t
1/2H-material,
H-material
(Light Annealed, Skin Hard)
ø22.2
[7/8"]
1.0t
ø25.4
[1"]
1.0t
ø28.58
[1-1/8"]
1.0t
ø31.75
[1-1/4"]
1.1t
ø34.93
[1-3/8"]
1.2t
ø41.28
[1-5/8"]
1.4t
Do not use the existing piping!
Содержание City Multi CMB-WP108V-G
Страница 1: ...AIR CONDITIONER 2014 Service Handbook PURY WP200 WP250YJM A CMB WP108V G Model 3rd edition ...
Страница 11: ... 2 HWE1113B GB ...
Страница 27: ... I Read Before Servicing 18 HWE1113B GB ...
Страница 29: ... 20 HWE1113B GB ...
Страница 57: ... 48 HWE1113B GB ...
Страница 70: ... III Outdoor Unit Components 61 HWE1113B GB 2 Power supply circuit board ...
Страница 71: ... III Outdoor Unit Components 62 HWE1113B GB ...
Страница 73: ... 64 HWE1113B GB ...
Страница 81: ... IV Remote Controller 72 HWE1113B GB ...
Страница 83: ... 74 HWE1113B GB ...
Страница 88: ... 79 HWE1113B GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 83 ...
Страница 89: ... 80 HWE1113B GB ...
Страница 97: ... 88 HWE1113B GB ...
Страница 127: ... 118 HWE1113B GB ...
Страница 135: ... VIII Test Run Mode 126 HWE1113B GB ...
Страница 137: ... 128 HWE1113B GB ...
Страница 252: ... 243 HWE1113B GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 245 ...
Страница 253: ... 244 HWE1113B GB ...