II
Restrictions ]
27
- 27 -
HWE1410A
GB
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC and OS), of the terminal block for indoor-out-
door transmission line (TB02) on the HBC controller
(HB), and of the terminal block for indoor-outdoor trans-
mission line (TB5) on each indoor unit (IC). (Non-polar-
ized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au-
tomatically designated as OC and OS in the order of ca-
pacity from large to small (if two or more units have the
same capacity, in the order of address from small to
large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor
units (OC and OS), the S terminal of the terminal block
(TB02) on HB, and the S terminal of the terminal block
(TB5) on the indoor unit (IC) with the shield of the shield-
ed cable.
2) Transmission line for centralized control
Daisy-chain terminals A and B on the system controller, termi-
nals M1 and M2 on the terminal block for transmission line for
centralized control (TB7) on the outdoor units (OC) in different
refrigerant circuits and on the outdoor units (OC and OS) (Note
a) in the same refrigerant circuit. (Note b)
When both of the following conditions are met, move the power
jumper connector on the control board from CN41 to CN40 on
only one of the outdoor units: (1) No power supply units are con-
nected to the transmission line for centralized control AND (2)
No controllers with a power-supply function are connected to
the system.
If a system controller is connected, set the central control switch
(SW2-1) on the control board of all outdoor units to "ON."
a) The outdoor units in the same refrigerant circuit are automatical-
ly designated as OC and OS in the order of capacity from large
to small (if two or more units have the same capacity, in the or-
der of address from small to large).
b) If TB7's on the outdoor units in the same refrigerant circuit are
not daisy-chained, connect the transmission line for the central
control system to TB7 of the OC. (Note a).To maintain the cen-
tral control even during an OC failure or a power failure, connect
TB7 on OC and OS together. (If there is a problem with the out-
door unit whose power jumper was moved from CN41 to CN40,
central control is not possible, even if TB7's are daisy-chained.)
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal of the terminal block (TB7) on the
system controller, OC, and OS with the shield of the shielded
cable. Short-circuit the earth terminal ( ) and the S terminal
on the terminal block (TB7) on the outdoor unit whose power
jumper connector is mated with CN40.
3) MA remote controller wiring
Same as [3] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [3] 1.
Group operation of indoor units
Same as [3] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on
the indoor unit (IC) to the appropriate terminals on the terminal
block for indoor-outdoor transmission line (TB5) on LOSSNAY
(LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man-
ual for the system controller for the setting method.) In-
terlock setting from the remote controller is required if the
ON/OFF remote controller alone or the LM adapter alone
is connected.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
Proce-
dures
Unit or controller
Ad-
dress
setting
range
Setting method
Notes
Fac-
tory
set-
ting
1
Indoor
unit
Main unit
IC
01 to
50
Assign the smallest address to the main unit
in the group.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
00
Sub unit
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit a1, main unit address
+2, main unit a3, etc.)
2
LOSSNAY
LC
01 to
50
Assign an arbitrary but unique address to
each of these units after assigning an address
to all indoor units.
None of these addresses may
overlap any of the indoor unit
addresses.
00
3
MA
remote
controller
Main
remote con-
troller
MA
No set-
tings re-
quired.
-
Make the same indoor unit
group settings with the system
controller as the ones that
were made with the MA remote
controller.
Main
Sub
remote con-
troller
MA
Sub
remote
controller
Settings to be made with the Sub/
Main switch
4
Outdoor unit (Note)
(Heat source unit)
OC
OS
51 to 100
Assign sequential address to the outdoor
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
To set the address to 100,
set the rotary switches to 50.
If the address that is as-
signed to the HBC controller
and Sub-HBC overlaps any
of the addresses that are as-
signed to the other units,
use a different, unused ad-
dress within the setting
range.
00
5
Auxiliary
outdoor
unit
HBC con-
troller
Sub-HBC
HB
HS
51 to 100 Assign an address that equals the lowest ad-
dress of the indoor units to be connected to
the HBC controller or Sub-HBC plus 50.
0000002394.book 27 ページ 2016年1月12日 火曜日 午後4時49分
Содержание CITY MULTI CMB-WP1016V-GA1
Страница 1: ......
Страница 9: ...HWE1410A GB ...
Страница 11: ... 2 HWE1410A GB ...
Страница 27: ... I Read Before Servicing 18 HWE1410A GB ...
Страница 29: ... 20 HWE1410A GB ...
Страница 47: ... 38 HWE1410A GB ...
Страница 50: ... III HBC Controller Components 41 HWE1410A GB 4 Top side 1 CMB WP1016V GA1 2 CMB WP108V GA1 VB3f VB3e ...
Страница 52: ... III HBC Controller Components 43 HWE1410A GB 2 Top side 1 CMB WP1016V GB1 2 CMB WP108V GB1 VB3f VB3e ...
Страница 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Страница 57: ... 48 HWE1410A GB ...
Страница 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Страница 68: ... 59 HWE1410A GB V Refrigerant Circuit 1 Refrigerant Circuit Diagram 61 2 Principal Parts and Functions 64 ...
Страница 69: ... 60 HWE1410A GB ...
Страница 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Страница 77: ... 68 HWE1410A GB ...
Страница 95: ... 86 HWE1410A GB ...
Страница 117: ... VII Test Run Mode 108 HWE1410A GB ...
Страница 119: ... 110 HWE1410A GB ...
Страница 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Страница 208: ... 199 HWE1410A GB IX LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 201 ...
Страница 209: ... 200 HWE1410A GB ...
Страница 292: ... IX LED Monitor Display on the Heat source Unit Board 283 HWE1410A 0000002394 book 283 ページ 2016年1月12日 火曜日 午後4時49分 ...
Страница 293: ... IX LED Monitor Display on the Heat source Unit Board 284 HWE1410A 0000002394 book 284 ページ 2016年1月12日 火曜日 午後4時49分 ...
Страница 294: ......