VIII
Troubleshooting ]
- 180 -
HWE1410A
GB
[7] Instructions for debris removal operation
This operation removes the debris that may have been introduced during installation from the water circuit.
Perform this operation
after completion of water- and refrigerant-piping work, air tightness test, evacuation
of refrigerant circuits, refrigerant charging, and electrical work.
1.Preparation for debris removal operation
2.Debris removal operation
3.End processing
2.Turn on the breaker, and then open the air vent valves on the HBC controller and the indoor units.
Refer to the Installation Manual for the location of air vent valves.
(If there are air vent valves on the field-installed pipes, open the valves as well.)
3.Supply water from the suction pipe on the HBC controller.
1.Set DIP SW 5-1 (valve opening when stopped), DIP SW 5-2 (nullification of drain over-flow error for 9 hours) from
off to on.
4.
Check that water comes from each air vent valve, and perform the debris removal operation.
1.If there are a large amount of debris in the water in the field-installed pipes, set DIPSW4-1 from OFF to ON.
(Refer to the flowchart for debris removal operation for details.)
Set the dipswitches 5-1 and 5-2 to OFF after completion of debris removal operation.
2. Forty minutes after the completion of debris removal operation, the LED will indicate "Air0." The LED indication will
change to "Air1," "Air2," and "AirE" in order. Then, the water pump will stop.
3.Stop the water supply, and check that no water is coming out of the air vent valves. Then, set the dipswitch 4-1 from ON to OFF.
(1)To avoid malfunction, do not connect or disconnect the power connector of the water pump being powered on.
(2)Check for water leaks from the field-installed pipe joint during operation.
(3)Do not pull the clip on the connection of the water pipe with pliers so that undue force is applied.
(4)If Error appears on the LED, turn off the breaker, turn it back on, and start over at step 2-1.
4.Set DIP SW4-6 to on, and switch off the HBC controller. Open the air-vent valve and the water-vent valve.
Slowly open the strainer closest to the water supply to the HBC. (Note that if it is opened fast, water may blast out.)
Remove the strainer, clean its inside, and refit it.
5.Slowly open the other strainer which is the furthest from the water supply.
(After the cleaning, set DIPSW4-6 to OFF.)
6.Make sure the strainers are re-installed.
<General cautions>
Step 1
Step 2
(1)The operation can be forced to stop by setting DIPSW4-4 from OFF to ON.
(2)If it is found during any step that air ventilation has not been completed to the desired degree, start over at Step 2-1.
The operation is performed while air is
discharged from the water pipe. [Air1]
Debris in the pipe will accumulate into the
strainer by operating all indoor units. [Air2 to AirE]
Intermittent operation of water pump (20 min)
Operation of all indoor units (20 min)
Flowchart for debris removal operation (DIPSW4-1 is ON.)
Perform the debris removal operation. (Each air vent valve should stay open.)
Install a non-return valve to prevent water in the water circuit
flowing back to the water supply pipe, or remove the water
supply hose after the air vent operation.
LED and DIPSW positions
HBC controller
Indoor unit (Example: PEFY-WP-VMA-E)
0000002394.book 180 ページ 2016年1月12日 火曜日 午後4時49分
Содержание CITY MULTI CMB-WP1016V-GA1
Страница 1: ......
Страница 9: ...HWE1410A GB ...
Страница 11: ... 2 HWE1410A GB ...
Страница 27: ... I Read Before Servicing 18 HWE1410A GB ...
Страница 29: ... 20 HWE1410A GB ...
Страница 47: ... 38 HWE1410A GB ...
Страница 50: ... III HBC Controller Components 41 HWE1410A GB 4 Top side 1 CMB WP1016V GA1 2 CMB WP108V GA1 VB3f VB3e ...
Страница 52: ... III HBC Controller Components 43 HWE1410A GB 2 Top side 1 CMB WP1016V GB1 2 CMB WP108V GB1 VB3f VB3e ...
Страница 55: ... III HBC Controller Components 46 HWE1410A GB 2 Power supply circuit board ...
Страница 57: ... 48 HWE1410A GB ...
Страница 67: ... IV Electrical Wiring Diagram 58 HWE1410A GB ...
Страница 68: ... 59 HWE1410A GB V Refrigerant Circuit 1 Refrigerant Circuit Diagram 61 2 Principal Parts and Functions 64 ...
Страница 69: ... 60 HWE1410A GB ...
Страница 75: ... 66 V Refrigerant Circuit GB HWE1410A ...
Страница 77: ... 68 HWE1410A GB ...
Страница 95: ... 86 HWE1410A GB ...
Страница 117: ... VII Test Run Mode 108 HWE1410A GB ...
Страница 119: ... 110 HWE1410A GB ...
Страница 207: ... VIII Troubleshooting 198 HWE1410A GB ...
Страница 208: ... 199 HWE1410A GB IX LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 201 ...
Страница 209: ... 200 HWE1410A GB ...
Страница 292: ... IX LED Monitor Display on the Heat source Unit Board 283 HWE1410A 0000002394 book 283 ページ 2016年1月12日 火曜日 午後4時49分 ...
Страница 293: ... IX LED Monitor Display on the Heat source Unit Board 284 HWE1410A 0000002394 book 284 ページ 2016年1月12日 火曜日 午後4時49分 ...
Страница 294: ......