–56–
YES
NO
YES
NO
YES
YES
NO
NO
Normal operations
Trouble observed
Stop
Start
Breaker
turned on
Set indoor ad-
dress No. to remote
controller
Operation
command
Operation
mode
Error mode
Cooling-only, Heating-only,
Cooling/heating mixed
Error stop
Operation
mode
Operation
mode
52C ON
[4] Operation Flow Chart
(1)
Heat source unit
Note : 1
For about 3 minutes after turning on power source, address and group information of heat source unit, BC, controller indoor
unit, and remote controller are retrieved by remote controller, during which “HO” blinks on and off on remote controller. In case
indoor unit is not grouped to remote controller, “HO” display on remote controller continues blinking even after 3 minutes after
turning on power source.
Note : 2
Two trouble modes included indoor unit side trouble, (BC controller trouble) and heat source unit side trouble. In the case of
indoor unit side trouble, error stop is observed in heat source unit only when all the indoor units are in trouble. However, if one
or more indoor units are operating normally, heat source unit shows only LED display without undergoing stop.
Note : 3
On PUHY system, operation mode conforms to mode command by indoor unit. However, when heat source unit is being under
cooling operation, the operation of indoor unit will be prohibited even by setting a part of indoor units under operation, or indoor
unit under stopping or fan mode to heating mode. Reversely when heat source unit is being heating operation, the same
condition will be commenced.
On PURY system, operation mode conforms to mode command by BC controller.
Note : 4
In case BC controller issues cooling/heating mixed operation mode, heat source unit decides operation mode of cooling-main
operation or heating-main operation.
Note : 3
Note : 2
Note : 1
Fan
“HO” blinks on the remote
controller
Oil return LEV (SLEV), INV
cooling LEV (LEV2) fully closed
1. 52C
OFF
2. Inverter output
0Hz
3. All solenoid valve
OFF
Cooling (Cooling-
only) operations
Heating (Heating-
only) operations
Cooling-main
operations
Heating-main
operations
Operation mode command to (BC controller) heat source unit
Error code blinks on the
outdoor controller board
Error command to
BC controller
Error code blinks on the
remote controller
Cooling/heating mixed
Note : 4
Содержание CITY MULTI CMB-P1010V-E
Страница 15: ... 12 RELAY board ...
Страница 16: ... 13 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 BC board ...
Страница 17: ... 14 RELAY 10 board RELAY 4 board ...
Страница 38: ... 35 ...
Страница 96: ... 93 ...
Страница 151: ......
Страница 152: ......
Страница 153: ......