[7] External Input/Output Specifications
(1)
Output
1
Operation ON signal
Terminal No.
TB8-1, 2
Output
Relay contacts output
Rated voltage: L1 - N: 220 ~ 240 V
Rated load: 1 A
Operation
•
When DIP switch 2-7 is OFF
The relay closes during compressor operation.
•
When DIP switch 2-7 is ON
The relay closes during reception of the cooling or the heating operation signal from the controller.
(Note: It is output even if the thermostat is OFF (when the compressor is stopped).)
2
COMP ON/OFF signal
Connector No.
CN51-3, 4
Connector : B5B-XH-A (JST)
Output
DC 12 V
Operation
DC 12 V is output during compressor operation.
3
Water freeze / trouble signal
Connector No.
CN51-3, 5
Connector : B5B-XH-A (JST)
Output
DC 12 V
Operation
•
When DIP switch 3-3 is OFF
If the water temperature (TH 6) drops below 5
°
C while the unit is stopped, DC 12 V is output.
•
When DIP switch 3-3 is ON
DC 12 V is output when the heat source unit is stopped abnormally.
(2)
Input
1
Pump Interlock
Terminal No.
TB8-3, 4
Input
Level signal
Operation
If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.
2
Demand
Connector No.
CN3D-1, 3
Connector : B3B-EH (JST)
Input
Level signal
Operation
If the circuit between CN3D-1 and CN3D-3 is opened, compressor operation is prohibited.
Содержание CITY MULTI CMB-P1010V-E
Страница 15: ... 12 RELAY board ...
Страница 16: ... 13 BC controller CNTR CN02 M NET transmission CN03 CN12 Power supply 1 EARTH 3 N 5 L SW4 SW2 SW1 BC board ...
Страница 17: ... 14 RELAY 10 board RELAY 4 board ...
Страница 38: ... 35 ...
Страница 96: ... 93 ...
Страница 151: ......
Страница 152: ......
Страница 153: ......