Switch
SWA
Ceiling
height
selector
SWB
Discharge
outlet
number
selector
SWC
Option
selector
Rotary switch
Rotary switch
SW14
Branch
No.
setting
SW11
1s digit
address
setting
SW12
10s digit
address
setting
Pole
(High ceiling)
(Standard)
(Silent)
3
2
1
(2
direction
)
(3
direction
)
(4
direction
)
2
3
4
(Option)
(Standard)
2
1
2
1
1–3
3
2
Operation by switch
Note: Ceiling height can be changed
depending on SWB setting.
When attaching the optional high performance
filter elements (multi function casement) to
the unit, be sure to attach it to the option
side in order to prevent the airflow reducing.
Remarks
<Initial setting>
Address board
<Initial setting>
Address board
<Initial setting>
Address board
Address board
<Initial setting>
Address board
3
2
1
2
3
4
SW12
10
SW11
1
SW12
SW11
SW14
SW14
<
Initial setting
>
Effective
timing
Before
power
supply
ON
Under
operation
or
suspension
1
Silent
8.2 ft [2.5 m]
8.9 ft [2.7 m]
9.8 ft [3.0 m]
2
Standard
8.9 ft [2.7m]
9.8 ft [3.0 m]
10.8 ft [3.3 m]
3
High ceiling
11.5 ft [3.5 m]
11.5 ft [3.5 m]
11.5 ft [3.5 m]
4 direction
3 direction
2 direction
SWA
SWB
PLFY-P08/12/15/18/24/30NBMU-E2
PLFY-P36NBMU-E2
4
3
2
1
Silent
8.9 ft [2.7 m]
9.8 ft [3.0 m]
10.8 ft [3.3 m]
2
Standard
10.5 ft [3.2 m]
11.8 ft [3.6 m]
13.1 ft [4.0 m]
3
High ceiling
14.8 ft [4.5 m]
14.8 ft [4.5 m]
14.8 ft [4.5 m]
4 direction
3 direction
2 direction
SWA
SWB
4
3
2
How to set address
Example : If address is "3", remain SW12
(for over 10) at "0", and match SW11 (for 1 to 9)
with "3".
How to set branch number SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC
controller’s end connection number
Remain other than series R2 at "0".
The black square (■) indicates a switch position.
OCH579