27
SW3-5
SW3-6
Vane setting
Initial setting
●
Setting
Vane position
OFF
OFF
Set up
1
Standard
Standard
ON
OFF
Set up
2
Less draft *
Upward position than the standard
OFF
ON
Set up
3
Less smudging
Downward position than the standard
ON
ON
unused
—
—
* Be careful of the smudge on ceiling.
Switch
Function
Remarks
Effective
timing
Under
suspension
Under
suspension
Before
power
supply
ON
Before
power
supply
ON
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Address board
Operation by switch
ON
OFF
*
1
Fan operation at Heating mode
*
2
Heat thermo-ON is operating.
Pole
Built-in remote controller
Provided
2,500 hr
Effective
Always operated while the heat in ON*
1
Low*
3
Setting air flow*
3
Effective
Effective
Filter clogging detection
Filter cleaning
Fresh air intake
Humidifier control
Air flow set in case of
Heat thermo-OFF
Auto restart function
Power ON/OFF by breaker
Indoor unit
Not provided
100 hr
Not effective
Operated depends on the condition*
2
Extra low*
3
Depends on SW1-7
Not effective
Not effective
Cooling only
Available
Available
Available
Second setting*
4
Third setting*
4
Effective
Not effective
—
—
Heat pump/Cooling only
Louver/Humidifier
Vane
Vane swing function in heating
(wave-flow)
Vane horizontal angle
1
Vane horizontal angle
2
Sensible temperature correction
Superheat setting temperature*
5
Sub cool setting temperature*
5
Heat pump
Not available
Not available
Not available
First setting*
4
Depends on SW3-5
Not effective
Effective
—
—
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
SW2
Capacity
code
setting
1–6
1–5
SW3
Function
setting
Thermistor <Room temperature
detection> position
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Indoor controller board
Indoor controller board
<Initial setting>
Set for each capacity.
Indoor controller board
SW1
Function
setting
SW4
Model
Selection
(Setting
for
PLFY
series)
Changing the opening of
linear expansion valve
Switching remote display Thermo ON signal display Indicating fan operation
ON/OFF
SW1-7
OFF
ON
OFF
ON
OFF
Extra low
Low
Setting air flow
Stop
OFF
ON
ON
SW1-8
*
3
Note :
*
4
SW3-5,6
*
5
Please do not use
SW-3-9,10 as trouble
might be caused by the
usage condition.
1 2 3 4 5
ON
OFF
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
MODEL
SW2
SW2
ON
OFF
1 2 3 4 5 6
PLFY-P08NBMU-E2
MODEL
PLFY-P12NBMU-E2
PLFY-P15NBMU-E2
PLFY-P18NBMU-E2
PLFY-P24NBMU-E2
PLFY-P30NBMU-E2
PLFY-P36NBMU-E2
9-2. FUNCTION OF DIP SWITCH
The black square (■) indicates a switch position.
OCH579