![Mitsubishi Electric Citi Multi Series Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/mitsubishi-electric/citi-multi-series/citi-multi-series_technical-and-service-manual_237995016.webp)
16
MICROPROCESSOR CONTROL
8
.
INDOOR UNIT CONTROL
8-1. COOL OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display COOL.
3
Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 2°F when the or button is
pressed one time. Cooling 67 to 87°F
Control modes
Control details
1-1. Determinating thermostatic control function
(Function to prevent restarting for 3 minutes)
• Room temperature
]
desired tempe 2°F ···Thermo-ON
• Room temperature
[
desired temperature ···Thermo-OFF
1-2. Anti-freezing control
Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16
minutes from compressors start up, anti-freezing control
starts and the thermo OFF.
Released condition : The timer which prevents reactivating is set for 3 minutes,
and anti-freezing control is cancelled when any one of the
following conditions is satisfied.
1
Liquid pipe temp. (TH22) turns 50°F or above.
2
The condition of the thermo OFF has become complete
by thermostat, etc.
3
The operation modes became mode other than COOL.
4
The operation stopped.
By the remote controller setting (switch of 4 Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Room temperature - Desired temperature
2. Fan
1. Thermostatic
control function
Remarks
Type
Fan speed notch
[Low], [Med2], [Med1], [High], [Auto]
4 Auto type
Continue to the next page
OCH579